SKE4 Steam Humidifier
LonWorks Integration Manual
www.neptronic.com
Page | 12
No.
Snivet Name
Full Name
Snivet Type
Notes
47
nvoBlrState
Boiler State
SNVT_count
Displays the current state of operation of the humidifier.
0 = Off
1 = Idle
2 = LineRinse
3 = TankRinse
4 = Filling
5 = Draining
6 = Heating
7 = Boiling
8 = Alarm
48
nvoBlrAlarm
Boiler Alarm
SNVT_count
Displays the current status of the humidifier alarm.
0 = Normal
1 = FailedPump
2 = FillTimeout
3 = BlockedPiping
4 = HeatTimeout
5 = Overheat
6 = WaterLeak
7 = Service
8 = Foaming
49
nviMCULoad
MCU Load
SNVT_count_inc_f
Value of the current microcontroller load.
0% to 100%, Resolution 0.1%
50
nviMemLoad
Memory Load
SNVT_count_inc_f
Value of the current memory load.
0% to 100%, Resolution 0.1%
51
nviLangEnglish
Language
SNVT_count
Value of the language setting.
52
nviUnits
Units
SNVT_count
Configuration value to select the display units for the LonWorks
module.
53
nviCtrlInput
Control Input
SNVT_count_inc_f
Value of the current control input reading.
0% to 100%, Resolution 0.01%
Only used if configured for analog external demand
54
nviRmRH
Room RH
SNVT_count_inc_f
Value of the room humidity reading. 0% RH to 100% RH,
Resolution 0.01% RH
Only used if configured for analog internal demand
55
nviSupHiLimRH
Supply High Limit RH
SNVT_count_inc_f
Value of the supply high limit humidity reading. 0% RH to 100% RH,
Resolution 0.01% RH
Only used if modulating high limit is used