SKE4 Steam Humidifier
LonWorks Integration Manual
www.neptronic.com
Page | 13
No.
Snivet Name
Full Name
Snivet Type
Notes
56
nviWtrLvlLow
Water Level Low
SNVT_switch
Status value of the resistive low water level sensor.
0 = Inactive, 1 = Active
57
nviWtrLvlHi
Water Level High
SNVT_switch
Status value of the resistive high water level sensor.
0 = Inactive, 1 = Active
58
nviWtrTmp
Water Temperature
SNVT_count_inc_f
Value of temperature of water in the evaporation chamber.
32°F to 257°F or 0°C to 125°C
Resolution 0.02°F or 0.01°C
59
nviFoamCutout
Foam Cutout
SNVT_switch
Displays whether foam has been detected within the evaporation
chamber. If Foam is displayed, it indicates that the Anti-Foaming
Energy Conservation (AFEC) system has detected foam. The
humidifier will drain for a few minutes and return to normal operation.
0 = No Foam, 1 = Foam
60
nviBoardTmp
Board Temperature
SNVT_count_inc_f
Displays the value of the PCB temperature.
32°F to 212°F or 0°C to 100°C.
Resolution 0.18°F or 0.10°C.
61
nviWtrLvlVlv
Water Level Valve
SNVT_switch
Displays the status of the water level sensor supply valve.
0 = Off, 1 = On
62
nviTnkWtrVlv
Tank Water Valve
SNVT_switch
Displays the status of the evaporation chamber water supply valve.
0 = Off, 1 = On
63
nviDrnCoolerVlv
Drain Cooler Valve
SNVT_switch
Displays the status of the internal drain cooler valve.
0 = Off, 1 = On
64
nviDrnPump
Drain Pump
SNVT_switch
Displays the status of the drain pump.
0 = Off, 1 = On
65
nviMainCont
Main Contactor
SNVT_switch
Displays the status of the main contactor.
0 = Off, 1 = On
66
nviHtrStg1
Heater Stage 1
SNVT_switch
Displays the status of the first stage contactor.
0 = Off, 1 = On
67
nviHtrStg2
Heater Stage2
SNVT_switch
Displays the status of the second stage contactor.
0 = Off, 1 = On
68
nviHtrStg3
Heater Stage 3
SNVT_switch
Displays the status of the third stage contactor.
0 = Off, 1 = On