SKE4 Steam Humidifier
LonWorks Integration Manual
www.neptronic.com
Page | 15
No.
Snivet Name
Full Name
Snivet Type
Notes
81
nviHumDem
Humidity Demand
SNVT_count_inc_f
Value of the current humidity demand.
0% to 100%, Resolution 0.01%
Only used if configured for network external demand.
82
nviSysStmOutput
System Steam Output
SNVT_count_inc_f
Value of the measured steam output of the humidifier.
0% to 100%, Resolution 0.01%
83
nviBlrDem
Boiler Demand
SNVT_count_inc_f
Value of the measured humidity demand of the humidifier.
0% to 100%, Resolution 0.01%
84
nviBlrRequest
Boiler Request
SNVT_count
Select whether to perform one of the following actions:
0 = None
1 = Reset Alarms
2 = Drain
3 = Reset Counters
4 = Filling
5 = WaterCalib
85
nviBlrState
Boiler State
SNVT_count
Displays the current state of operation of the humidifier.
0 = Off
1 = Idle
2 = LineRinse
3 = TankRinse
4 = Filling
5 = Draining
6 = Heating
7 = Boiling
8 = Alarm
86
nviBlrAlarm
Boiler Alarm
SNVT_count
Displays the current status of the humidifier alarm.
0 = Normal
1 = FailedPump
2 = FillTimeout
3 = BlockedPiping
4 = HeatTimeout
5 = Overheat
6 = WaterLeak
7 = Service
8 = Foaming