SKE4 Steam Humidifier
LonWorks Integration Manual
www.neptronic.com
Page | 6
Configuration
For the BACnet IP module of the humidifier, ensure that the following settings inside of the
Integration
menu are
properly set:
Select the
IPSettings
option, then select the
DHCP
setting and modify the value of its parameter to
Inactive
.
Select the
StaticAddress
setting and modify the value of its parameter to
192.168.00.001.
Select the
StaticSubnetMask
setting and modify the value of its parameter to
255.255.255.0.
Select the
StaticDefaultGateway
setting and modify the value of its parameter to
192.168.0.000.
Select the
RstIPSetting
setting and modify the value of its parameter to
Yes
, in order to enable the new IP
configurations.
The ProtoCessor node already arrives with the APB file preloaded and the Config table file for the Snivet to BACnet
data conversion.
If diagnostic data is required, the ProtoCessor node has a built-in web server and, if an Ethernet switch is installed,
can be accessed at the following address:
192.168.00.00
.
Software Files
XIF:
This is the device template of the humidifier for the integrator. When binding a node onto the network, a XIF file is
needed. The XIF file has information that is used by the network management tool to help ease the installation and
maintenance process of a node. It can also be used for offline configuration of the node.
File name:
SKE4lon.xif
File created:
November
14:01:39
File PID:
90:00:95:47:1E:02:04:66
APB:
When running an application program associated with a XIF file, an APB file is needed. Please note that the
ProtoCessor Node has the APB file already flashed from the factory with the proper settings.
Device Resource File (DRF):
There is no DRF format files associated with this device. All objects are fully declared
as standard Echelon snivets.
LnmL (Niagara Tridium Integration File):
This is the device template of the humidifier for the Tridium / Niagara AX
integrator.
File name:
SKE4lon.lnml
File created:
14:03
File PID:
90:00:95:47:1E:02:04:66