SKE4 Steam Humidifier
LonWorks Integration Manual
www.neptronic.com
Page | 8
Standard Network Variables Types (SNVT) Table
No.
Snivet Name
Full Name
Snivet Type
Notes
0
nvoMCULoad
MCU Load
SNVT_count_inc_f
Value of the current microcontroller load.
0% to 100%, Resolution 0.1%
1
nvoMemLoad
Memory Load
SNVT_count_inc_f
Value of the current memory load.
0% to 100%, Resolution 0.1%
2
nvoLangEnglish
Language
SNVT_count
Value of the language setting.
3
nvoUnits
Units
SNVT_count
Configuration value to select the display units for the LonWorks
module.
4
nvoAirFlow
Air Flow
SNVT_switch
Status of the airflow switch.
If the switch is Open, it indicates that the airflow is not detected by
the air pressure switch.
0 = Closed, 1 = Open
5
nvoSupHiLim
Supply High Limit
SNVT_switch
Status of the high limit contact.
If the switch is Open, it indicates that the humidity level has exceeded
the setpoint on the high limit humidistat.
0 = Closed, 1 = Open
6
nvoInterlock
Interlock
SNVT_switch
Status of the interlock.
If the switch is Open, it indicates that the humidifier is stopped as a
result of the interlock safety being open.
0 = Closed, 1 = Open
7
nvoBiExtDem
Binary External Demand
SNVT_switch
Displays whether there is currently a humidity demand, when an
On/Off humidifier is used.
0 = 0%, 1 = 100%
Only used if configured for ON/Off control mode.
8
nvoCtrlSig
Control Signal Type
SNVT_count_inc_f
Displays the signal type for the control demand analog input.
0 = 0 to 10Vdc
1 = 2 to 10Vdc
2 = 4 to 20mA
3 = 0 to 20mA
9
nvoCtrlInput
Control Input
SNVT_count_inc_f
Value of the current control input reading.
0% to 100%, Resolution 0.01%
Only used if configured for analog external demand.