SKE4 Steam Humidifier
LonWorks Integration Manual
www.neptronic.com
Page | 9
No.
Snivet Name
Full Name
Snivet Type
Notes
10
nvoRmRHSig
Room RH Signal Type
SNVT_count_inc_f
Displays the signal type for the room humidity analog input.
0 = 0 to 10Vdc
1 = 2 to 10Vdc
2 = 4 to 20mA
3 = 0 to 20mA
Only used if configured for analog internal demand.
11
nvoRmRH
Room RH
SNVT_count_inc_f
Value of the room humidity reading.
0% RH to 100% RH, Resolution 0.01% RH
Only used if configured for analog internal demand.
12
nvoSupRHSig
Supply RH Signal Type
SNVT_count_inc_f
Displays the signal type for the duct or supply high limit humidity
analog input.
0 = 0 to 10Vdc
1 = 2 to 10Vdc
2 = 4 to 20mA
3 = 0 to 20mA
Only used if configured for analog internal demand.
13
nvoSupHiLimRH
Supply High Limit RH
SNVT_count_inc_f
Value of the supply high limit humidity reading.
0% RH to 100% RH, Resolution 0.01% RH
Only used if a modulating high limit is used.
14
nvoWtrLeakDet
Water Leak Detection
SNVT_switch
Displays whether there is a water leak detection.
0 = OK, 1 = Leak
15
nvoWtrLvlLow
Water Level Low
SNVT_switch
Status value of the resistive low water level sensor.
0 = Inactive, 1 = Active
16
nvoWtrLvlHi
Water Level High
SNVT_switch
Status value of the resistive high water level sensor.
0 = Inactive, 1 = Active
17
nvoWtrTmp
Water Temperature
SNVT_count_inc_f
Value of temperature of water in the evaporation chamber.
32°F to 257°F or 0°C to 125°C
Resolution 0.18°F or 0.10°C
18
nvoFoamCutout
Foam Cutout
SNVT_switch
Displays the status of the foaming sensor input. If the switch is Open,
it indicates that a normal state of operation without foam.
0 = No Foam 1 = Foam Present
19
nvoThermalCutout
Thermal Cutout
SNVT_switch
Displays the status of the high temperature switch. If the switch is
Open, it indicates that an abnormal temperature has been detected.
0 = Closed, 1 = Open