SKG3 Gas Fired Humidifier
Installation Instructions and User Manual
14
Stage 2
– Steam Distribution Installation
Steam Outlet
Configuration for
Weather Proof
Enclosure
Weather proof enclosure single steam outlet - Fig. 17
The SKG3 humidifier with weather proof enclosure is provided with an integrated
steam manifold with an outlet located on either one of the sides of the humidifier.
By default, the steam outlet will be on the right side of the humidifier (when facing the
control panel). Steam outlet side can be switched to left upon request to factory.
Weather Proof
Enclosure Steam
Outlet Dimension
& Quantity
Model
Steam outlet
Qty
Steam outlet
diameter
SKG3
110-1, 155-1, 180-1, 210-1
1
Ø
3”
(76mm)
SKG3
265-2, 310-2, 350-2, 405-2
1
Ø
4”
(100mm)
SKG3
505-3, 560-3, 610-3
1
Ø
5”
(125mm)
SKG3
710-4, 765-4, 810-4
2
Ø4
”
(100mm)
Integrated steam manifold
Steam outlet