SKG3 Gas Fired Humidifier
Installation Instructions and User Manual
1
Safety
WHAT TO DO
IF YOU SMELL
GAS!
Do not try to light any appliances.
Do not touch any electrical switches; do not use any telephones in your building.
Immediately call your gas supplier from an off-site telephone.
Follow the gas supplier's instructions.
If you cannot reach your gas supplier, call the fire department.
GAS
Before installation, check that the local distribution conditions, nature of gas and
pressure, and the current state adjustment of the appliance are compatible.
Improper installation, adjustment, alteration, service, maintenance or use can
cause carbon monoxide poisoning, explosion, fire, electrical shock or other
conditions which may cause personal injury or property damage.
This appliance MUST be used only in sufficiently ventilated space. Consult
instructions before installation and use of this appliance.
Installation and service MUST be performed by a qualified gas installer, service
agency, or the gas supplier.
Ensure that local regulations concerning the provision of gas installations are
followed.
ELECTRICITY
All work concerned with electrical installation MUST only be performed by skilled and
qualified technical personnel (e.g. electrician or technician with appropriate training).
The customer is always responsible for ensuring the suitability of the technical
personnel.
Ensure that the local regulations concerning the provision of electrical installations
are followed.
HEALTH &
SAFETY
Neptronic has considered aspects of the design of their humidification systems to
reduce as much
as possible the risk of Legionnaires’ disease and other similar
conditions, but it is important that users are also aware of their responsibilities.
To prevent the growth of Legionella, users are required to:
Avoid water temperature that favors the growth of Legionella (20-45
˚C [68 to
113
˚F]).
Avoid water stagnation.
Clean and disinfect the humidification system.
Have a competent person carry out a risk assessment of the water system
supplying the humidifier to ensure the water supply is of an acceptable
quality.
CORRECT USE
Neptronic® systems and products are designed only for humidification use.
Any other application is not considered as usage for the intended purpose. The
manufacturer cannot be made liable for any damage resulting from incorrect use.
ACCESS
The SKG3 cabinet keys MUST never be left in the door locks, as this may cause
unauthorized access to live electrical parts. Always store keys centrally with a
nominated responsible person.
WATER
Neptronic® systems are designed to be used with tap, reverse osmosis,
demineralized or partially softened water. On no account attempt to introduce any
other fluids or chemicals into the system without first consulting Neptronic or its
authorized distributor.
Water supply must not exceed the max pressure of 70 psig (480 kPa), or pressure
limits laid out in the Installation Instructions and User Manual, and must comply with
local regulations.
!
!