SKG3 Gas Fired Humidifier
Installation Instructions and User Manual
19
Stage 2
– Steam Distribution Installation
SKG3-505 to 610
Steam pipe work 3 modules - Fig. 28
(dimensions in bracket are in mm)
Three
Ø3’’ (76mm) steam outlets to a single Ø5 ¼’’ (133mm) feed pipe must be
connected to a double Multi-Steam with a suitable reduction at the lowest point to
allow a
ؽ’’ (15mm) condensate drain from the main steam supply.
If these
Ø ½’’ (15mm) condensate pipes are connected, the common condensate
drain must be
ؾ’’ (22mm).
SKG3-710 to 810
Steam pipe work 4 modules, Multi-Steam - Fig. 29
(dimensions in bracket are in mm)
Two
Ø3’’ (76mm) steam outlets to a single Ø4 ¼’’ (108mm) feed pipe must be
connected to a single Multi-Steam with a suitable reduction at the lowest point to
allow a
Ø ½’’ (15mm) condensate drain from the main steam supply.
This must be reproduced two times.
If the two
ؽ’’ (15mm) condensate pipes are connected, the common condensate
drain must be
ؾ’’ (22mm).
ؾ'’ (22)
Ø3'’ (76) (x3)
Ø5 ¼'’ (133)
Min. 7° pipe slope
Insulated pipe
Air Duct
ؽ'’ (15)
Static pressure
+ 2'’ (50)
min
7° p
ipe s
lope
min
7° p
ipe s
lope
ؽ'’ (15)
Static pressure
+ 2'’ (50)
ؾ'’ (22)
Min. 7° pipe slope
Insulated pipe
Air Duct
Ø3'’ (76)
(x2)
Ø4 ½'’
(108)
x2