SKG3 Gas Fired Humidifier
Installation Instructions and User Manual
40
Control Set-up Menu
Display
Description
Values
Control Mode:
Selection of control mode.
If External is selected, the control demand will be received
by the analog input. If Com Port is selected, the control
demand will be received by the communication port
(BACnet option).
External
Internal
Com Port
Control Input Setup:
Selection of input control settings.
Allows you to select the voltage or current signal and the
range of the signal.
Voltage or Amp.
From 0 to 10 V
or 2 to 10 V
Or 4 to 20 mA
Room SP Source:
Selection of source for room humidity setpoint.
External
Internal
Com Port
Room Set Point:
Selection of room relative humidity value.
Percentage
From 10 to 90 %
Room Humidity SetPoint:
Selection of room humidity setpoint settings.
Allows you to select voltage or current signal and range of
the signal.
Voltage or Amp.
From 0 to 10 V
or 2 to 10 V
Or 4 to 20 mA
Room RH Source:
Selection of room relative humidity source.
External
Com Port
Humidity Input Setup:
Selection of humidity input.
Voltage or Amp.
From 0 to 10 V
or 2 to 10 V
Or 4 to 20 mA
Humidity Input Offset:
Selection of room humidity input offset.
Offset in %
From -5.0% to +5.0%
Hi Limit Ctrl Mode:
Selection of high limit control mode.
Disable
External
Com Port
Hi Limit Set Point Adjustment:
Selection of high limit relative humidity value.
Percentage
From 50 to 90 %
CONTROL SETUP
200
Control Mode
INTERNAL
CONTROL SETUP
201
Control Input Setup
Volt/Amp: Voltage
Vin Min.: 2.00V
Vin Max.: 10.00V
CONTROL SETUP
202
Room SP Source
INTERNAL
CONTROL SETUP
203
Room Set Point
40 %
CONTROL SETUP
204
Room Humidity SetPoint
Volt/mA: Voltage
Vin Min.: 2.00V
Vin Max.: 10.00V
CONTROL SETUP
205
Room RH Source
EXTERNAL
CONTROL SETUP
206
Humidity Input Setup
Volt/Amp: Voltage
Vin Min.: 2.00V
Vin Max.: 10.00V
CONTROL SETUP
207
Humidity Input Offset
45.5%RH
Off: 0.00%
CONTROL SETUP
208
Hi Limit Ctrl Mode
Disable
CONTROL SETUP
209
Hi Limit SP Adjust.
80%