SKG3 Gas Fired Humidifier
Installation Instructions and User Manual
15
Stage 2
– Steam Distribution Installation
Selection of
Steam
Distribution
Manifolds
1.
The minimum steam manifold length that can be used with the SKG3-110-1 to
SKG3-210-1 is
35’’ (900mm). Any manifold below this dimension will have
insufficient outlet spigots to allow proper steam distribution.
2.
If duct size is below a width of
35’’ (900mm) width, it will be necessary to either fit
multiple pipes or use a Multi-Steam system.
Horizontal duct
– 2 manifolds - Fig. 18
(dimensions in bracket are in mm)
Horizontal duct
– 3 manifolds - Fig. 19
(dimensions in bracket are in mm)
Vertical duct
– 2 manifolds - Fig. 20
(dimensions in bracket are in mm)
Vertical duct
– 3 manifolds - Fig. 21
(dimensions in bracket are in mm)
H
2
/5
H
5'’ (120)
5
'’
(1
2
0
)
Ø 3'’ (78)
1
/5
H
8'’ (200)
air flow
Air duct
H
1
/3
H
5
'’
(1
2
0
)
Ø3'’ (78)
1
/6
H
10'’ (250)
air flow
Air duct
10'’ (250)
1
/2
H
5'’ (120)
H
min. 24'’ (600)
1/2 H
1/4 H
1/4 H
M
in
.
4
'’
(1
0
0
)
Air duct
H
min. 36'’ (900)
1/3 H
1/3 H
1/6 H
1/6 H
M
in
.
4
'’
(1
0
0
)
Air duct