SKG3 Gas Fired Humidifier
Installation Instructions and User Manual
18
Stage 2
– Steam Distribution Installation
Steam Pipe Work to Duct Connections (SKG3-110 to 810)
SKG3-110 to 265
Steam pipe work 1 module, Multi-Steam - Fig. 26
(dimensions in bracket are in mm)
A single
Ø3’’ (76mm) feed pipe must be connected to a single Multi-Steam with a
suitable reduction at the lowest point to allow a
ؽ’’ (15mm) condensate drain from
the main steam supply.
SKG3-265 to 405
Steam pipe work 2 modules, Multi-Steam - Fig. 27
(dimensions in bracket are in mm)
Two
Ø3’’ (76mm) steam outlets to a single Ø4 ¼’’ (108mm) feed pipe must be
connected to a single Multi-Steam with a suitable reduction at the lowest point to
allow a
ؽ’’ (15mm) condensate drain from the main steam supply.
Ø3'’ (76)
ؽ'’ (15)
Insulated pipe
Air duct
Static pressure
+ 2'’ (50)
Multisteam
Min. 7° pipe slop
Total length of steam conduit should
not exceed 17' (5m)
min
7° p
ipe s
lope
Ø3'’ (76)
Ø3'’ (76)
Ø4 ¼'’ (108)
Ø2'’ (15)
Min. 7° pipe slope
Static pressure
+ 2'’ (50)
Insulated pipe
Air Duct