SKG3 Gas Fired Humidifier
Installation Instructions and User Manual
39
Status Menu
Display
Description
Room Relative Humidity:
Displays the room relative humidity if a room humidistat is connected to the
humidifier.
System Demand:
Displays the humidity demand from the system.
100% represent a full demand.
System Output:
Displays the output for each module.
Value is indicated in %. (50% of a 500 lb/h module would represent 250 lb of steam
per hour output.)
Hours before drain:
Displays the remaining time before the next automatic flush for each module.
The automatic flush of the evaporation chamber is fully programmable. Please refer
to display # 301 for more details.
Note: If Drain has been disabled by an authorized service engineer, this display will
be disabled as well.
Running Hours:
Displays the number of hours of operation since the last servicing for each module.
Value is indicated in hours. This counter can be reset after each servicing.
Total Running Hours:
Displays the total number of hours of operation for each module since the original
start-up.
This counter cannot be reset.
Water level:
Displays the reading of water level electronic probe for each module.
Value is indicated in %. 100% indicate that the evaporation chamber is full of water.
During normal operation, the value can fluctuate between 95% and 105%.
Water Temperature:
Displays the water temperature inside the evaporation chamber for each module.
Value is indicated in
˚C. During normal operation, it must be around 212ºF (100ºC).
Chimney Temperature:
Displays the flue gases temperature for each module.
Value is indicated in
˚C. During normal operation, it must be lower than 410ºF (210ºC).
Unit Size:
Displays the total capacity of each module.
Value is indicated in lb/hr.
Note: Displays shown in these instructions represent a display for a 4 module SKG3 Steam humidifier. If your SKG3 Steam
humidifier is equipped with 1, 2 or 3 modules, only H1, H1 and H2, or H1, H2 and H3 will appear on the LCD display.
STATUS
101
Room Rel. Humidity
64%RH
STATUS
104
System Demand
64,3%
STATUS
105
System Output
H1: 45,5%
H2: 43,0%
H3: 42,5%
H4: 41,0%
STATUS
106
Hours before drain
H1: 4H
H2: 2H
H3: 3H
H4: 1H
STATUS
107
Running Hours
H1: 2H
H2: 2H
H3: 3H
H4: 1H
STATUS
108
Total Running Hours
H1: 40H
H2: 25H
H3: 22H
H4: 20H
STATUS
109
Water level
H1: 98%
H2: 99%
H3: 101%
H4: 98%
STATUS
110
Water Temperature
H1: 32°C
H2: 35°C
H3: 31°C
H4: 29°C
STATUS
111
Chimney Temperature
H1: 41°C
H2: 45°C
H3: 60°C
H4: 51°C
STATUS
112
Unit Size
H1: 110 lb/Hr
H2: 105 lb/Hr
H3: 103 lb/Hr
H4: 110 lb/Hr
All manuals and user guides at all-guides.com