SKG3 Gas Fired Humidifier
Installation Instructions and User Manual
41
Control Set-up Menu
Hi Limit SetPoint:
Selection of high Limit setpoint settings.
Allows you to select the voltage or current signal and the
range of the signal.
Voltage or Amp.
From 0 to 10 V
or 2 to 10 V
Or 4 to 20 mA
Hi Limit Offset:
Selection of duct relative humidity input offset.
Offset in %
From -5.0% to +5.0%
PID Control Band
Selection of PID control band value
Percentage
From 1 to 20 %
PID Control Gain
Selection of PID control gain values
KP from 0 to 100
KI from 0 to 100
KD from 0 to 100
Tank Operation:
Selection of tank operation, when SKG3 humidifier has
more than one module.
For optimum humidity control, it is recommended to use
sequential operation.
Sequential
Parallel
Lock On Capacity:
Selection of humidifier capacity reduction.
Percentage
From 20 to 100 %
CONTROL SETUP
210
Hi Limit SetPoint
Volt/mA: Voltage
Vin Min.: 2.00V
Vin Max.: 10.00V
CONTROL SETUP
211
Hi Limit Offset
45.5%RH
Off: 0.00%
CONTROL SETUP
212
PID Control Band
5.0 %
CONTROL SETUP
213
PID Control Gain
KP = 20
KI = 0
KD = 0
CONTROL SETUP
214
Tank Operation
SEQUENTIAL
CONTROL SETUP
215
Lock On Capacity
100 %