SKG3 Gas Fired Humidifier
Installation Instructions and User Manual
42
System Set-up Menu
Display
Description
Values
Service Timer:
Selection of delay between service alarms.
Value is indicated in Hours.
From 400 to 3000 Hrs
Increment: 100 Hrs
Default:1000 Hrs
Auto Drain Delay:
Selection of delay between automatic drain cycles.
Value is indicated in Hours.
Note: If Auto-Drain has been disabled by an authorized
service engineer
, this display will indicate “Drain Disabled’’.
From 1 to 24 Hrs
Increment: 1 Hr
Default:4 Hrs
No Demand Delay:
Selection of delay when there is no demand.
Value is indicated in Hours.
Note: If Auto-Drain has been disabled by an authorized
service engineer
, this display will indicate “EOS Disabled’’.
From 1 to 250 Hrs
Increment: 1 Hrs
Default:72 Hrs
Fan ON Delay:
Selection of delay to keep fan ON when there is no humidity
demand. If the fan is connected to the Operation volt free
contact, refer to stage 9.
Value is indicated in Minutes.
From 3 to 30 Min.
Increment: 1 Min.
Default:10 Min.
Holding Temperature:
Selection of evaporation chamber temperature between
humidity demands. If enabled, combustion will be ordered
to maintain a specific water temperature.
Value is indicated in
˚C, when setting is enabled.
From 50 to 90
˚C
or OFF
Increment: 5
˚C
Default: OFF
Anti Freeze Temperature:
Selection of evaporation chamber anti-freeze temperature.
If enabled, combustion will be ordered to maintain water
temperature between 7 and 12°C.
This feature must be enabled when using direct outside
combustion air in a freezing environment.
This screen is not available for humidifiers with the weather
proof enclosure option.
Value is indicated in
˚C, when setting is enabled.
From 7 to 12
˚C or OFF
Increment: 1
˚C
Default: OFF
Water Temperature Offset:
Selection of evaporation chamber temperature offset for
each module, in order to adjust reading of the water
temperature probe to proper temperature.
When producing water temperature, probe must indicate
100
˚C (212˚F).
Value is indicated in
˚C.
From -10 to 10
˚C
Increment: 1
˚C
Default: 0
˚C
Water Level Offset:
Selection of evaporation chamber water level offset for each
module, in order to adjust reading of the water level probe
to the proper level.
Value is indicated in
%.
From -10 to 10%
Increment: 1%
Default: 0%
SYSTEM SETUP
300
Service Timer
1000 Hrs
SYSTEM SETUP
301
Auto Drain Delay
4 Hrs
SYSTEM SETUP
302
No Demand Delay
72 Hrs
SYSTEM SETUP
303
Fan ON Delay
10 Min
SYSTEM SETUP
304
Holding Temperature
OFF
SYSTEM SETUP
305
Anti Freeze Temper.
OFF
SYSTEM SETUP
306
Water Temp. Offset
H1: 0°C
H2: 0°C
H3: 1°C
H4: -1°C
SYSTEM SETUP
307
Water Level Offset
H1: 0%
H2: -1%
H3: 2%
H4: 0%