SKG4-E Gas Fired Humidifier
Installation Instructions and User Manual
Page | - 16 -
Ambient Condition and Altitude
The humidifier location MUST have an ambient temperature of less than 30˚C.
If the above condition is not respected for indoor humidifiers, the warranty of the unit will be
void, as it has not been designed to operate under extreme external conditions.
The combustion burner of the SKG4 humidifier is self-adjusting for any altitude; the burner will
maintain proper combustion and low emission at any altitude.
Steam capacity will be affected by altitudes over 1050m above sea level. Please refer to the
table below to anticipate the ratio of output reduction.
Table 7 - Output Reduction Based on Altitude
Altitude Above Sea Level (m)
Output Reduction (%)
0 to 1050
0
1051 to 1350
2
1351 to 1650
4
1651 to 1950
6
1951 to 2250
8
Minimum Clearances
The following minimum clearances are indicated for inspection and servicing access. The
SKG4 humidifier is designed for a zero clearance to combustible materials.
Leave a clearance of at least 0.8 m to the front panel and 0.6 m on the left and right sides of
the humidifier.
Leave a clearance of at least 0.5 m on top of the humidifier.
24"
(0.6
m)
min
imu
m
2
0
"
(0
.5
m
)
m
in
im
u
m
30
" (
0.8
m)
mi
nim
um
24" (
0.6m
)
min
imu
m
Illustration 9 - Standard Enclosure Clearances