SKG4-E Gas Fired Humidifier
Installation Instructions and User Manual
Page | - 25 -
Steam Pipe Work to Duct Connections with Multi-Steam
Single Module Humidifiers: SKG4-E0501 to SKG4-E1001
Ø3" (76mm)
ؽ"
(15mm)
Insulated pipe
Air Duct
Static pressure
+ 2" (50mm)
Multi-Steam
Min. 7° pipe slope
Total length of steam conduit must not exceed 16ft (5m).
Illustration 23 - Multi-Steam Steam Pipe Work (SKG4-E0501 to 1001)
A single Ø76mm feed pipe must be connected to a single Multi-Steam with a suitable reduction at the
lowest point to allow a Ø15mm condensate drain from the main steam supply.
2 Module Humidifiers: SKG4-E1202 to SKG4-E2002
min
7° p
ipe s
lope
Ø3" (76mm)
Ø3" (76mm)
Ø4" (100mm)
Ø
½” (15mm)
Min. 7° pipe slope
Static pr
2" (50mm)
Insulated pipe
Air Duct
Total length of steam conduit must not exceed 16ft (5m)
Illustration 24 - Multi-Steam Steam Pipe Work (SKG4-E1202 to 2002)
Two Ø76mm steam outlets attached to a single Ø100mm feed pipe must be connected to a single
Multi-Steam with a suitable reduction at the lowest point to allow a Ø15mm condensate drain from the
main steam supply.