Stage 3 - Gas Supply Connection
Gas piping installation must comply with all local codes and regulations.
Any installation work must be carried out by suitably qualified personnel.
Gas pressure to the humidifier must never exceed 6kPa (60 mbar).
A manual shut off valve (not supplied) must be installed on the gas supply line to the
humidifier. Ensure adequate size for the gas supply line.
A DN6 (1/8” NPT) plugged tapping for test pressure gauge connection must be installed
immediately upstream of the gas supply line. Pressure tapings for test gauges must be
located at the gas valve.
It is recommended to use a separate pressure regulator for each humidifier connected to the
gas line. Ensure that the humidifier is not connected to the same regulator as any other gas
appliances.
Pipes must be inspected for dirt and chips after threading and reaming the end of pipes.
Gas piping installation must be supported to avoid mechanical strain/stress.
Two wrenches must be used when connecting gas piping to the humidifier.
Drip pocket must be provided at any low spot in the gas line.
Minimum gas pipe gradient must be 6.5mm per 1000mm horizontal run.
Air purge must be done by disconnecting piping at the gas valve. Air purge must not be done
at the heat exchanger of the humidifier.
After installation, field piping and humidifier gas train must be checked for leaks. Do not use
soap solution or open flame on the humidifier gas train. A gas leak detector must be used.
All leaks must be sealed prior to commissioning the humidifier.