SKG4-E Gas Fired Humidifier
Installation Instructions and User Manual
Page | - 28 -
Gas Pipe Diameter
Table 9 - Gas Connection Size
Model
Gas Connection Size
SKG4-E0501 to 2002
Ø25mm Male
SKG4-E2503 to 4004
Ø40mm Male
Refer to local codes and regulations regarding the type and volume of gas handled, in order to
obtain the pressure drop allowed in the gas line and determine the gas pipe diameter.
When multiple SKG4 humidifier modules are installed, consideration must be taken to total
capacity, gas flow and length of main.
SKG4
G
A
S
LI
N
E
⅛" NPT (DN6) Plugged Taping for
Test Pressure Gauge
¼ Turn Gas Valve
Drip Pocket
Illustration 27 - Gas Supply Connection
Gas Leak Test
Pressure testing of the gas supply piping must be performed by the gas installer in
accordance with local codes and regulations.
Test pressure must be relieved from the gas piping system prior to opening the manual shut-
off valve of the humidifier.
For any test pressure over 350kPa (3.5 bar), the humidifier must be disconnected (at the gas
shut-off valve).
The gas supply pressure at the inlet pressure tap, when all the burners are running, must be:
o
1.75 kPa (17.5 mbar) for natural gas.
o
3.5 kPa (35 mbar) for propane and butane.