SKG4-E Gas Fired Humidifier
Installation Instructions and User Manual
Page | - 2 -
Access
The SKG4 cabinet keys MUST never be left in the door locks, as this may cause unauthorized access
to live electrical parts. Always store keys centrally with a nominated responsible person.
Water
Neptronic systems are designed to be used with tap, reverse osmosis or deionized water. On no
account must any other fluids or chemicals be introduced into the system without first consulting
Neptronic or its authorized distributor.
Water supply must not exceed the max pressure of 4.8 bar or pressure limits laid out in the
specification and installation must comply with local regulations. Your attention is drawn to your
responsibilities as outlined in the Health and Safety regulations. The control of Legionella bacteria in
water systems and your SKG4 humidifier must be included in the risk assessment of the water system
in your building as a whole. In particular, if the humidifier is turned off for prolonged periods, you must
ensure that the unit is drained and that stagnation is avoided in pipe work supplying it.
A competent individual or organization must be appointed to carry out water tests. A wide range of
different tests are available to identify the presence of microbes in water, including total viable count
(TVC), temperature-range specific tests and identification of particular species types including
Legionella. It is the responsibility of the person on whom the statutory responsibility falls to determine
the type and frequency of this and all other controls and preventative measures outlined in this
manual.