SKG4-E Gas Fired Humidifier
Installation Instructions and User Manual
Page | - 32 -
SKG4
Main Drain
Pan Drain
Drain Trap
Main Drain
Illustration 30 - Water Drain Connections: Incorrect Installation
Pan Drain Connection on Weather Proof Enclosure
The weather proof enclosure is provided with a pan drain at the base of the SKG4 humidifier.
W
U
1/2xU
1/2xW
Pan drain outlet
Ø 0.6" (15mm)
Illustration 31 - Weather Proof Enclosure Base Pan Drain Outlet Dimension
Weather Proof Enclosure Water Drain Valve
The weather proof enclosure is equipped with a normally open valve, enabling the humidifier to drain
all water during a power failure, in order to prevent water from freezing within the unit. During normal
operation, the humidifier reduces drain water temperature to 60°C.
CAUTION:
During a power failure, the drain water temperature is not reduced. Installed
drain piping must be rated to 100°C.