SKG4-E Gas Fired Humidifier
Installation Instructions and User Manual
Page | - 34 -
Natural Ventilation Installation
Low level opening
High level opening
Outside
Wall
Humidifier’s air openings
Illustration 32 - Natural Ventilation Configuration
Ducted Combustion Air
The
“Ducted Combustion Air” option, also called Sealed Combustion, is available upon
request.
When
the “Ducted Combustion Air” option is installed, the requirements for minimum low level
and high level natural ventilation do not apply.
Installation of the combustion air duct must be as direct as possible, minimizing the number of
turns or elbows, with a maximum of 6 elbows in total.
Use only duct materials suitable to supply air from the outside to the humidifier.
Combustion air duct length and flue gas venting pipe must not exceed:
o
30m
– 3m x (total number of 90˚elbow) – 1.5m x (total number of 45˚elbow).
Combustion air duct must be insulated to avoid condensing around the duct when outside air
temperature is below 0˚C.
Ensure that the combustion air duct connections are air tight.
The minimum combustion air duct upward gradient must be 20mm in 1000mm horizontal run.
Model
Combustion Air Inlet
Diameter per Module
SKG4-EXXXX
Ø51mm O.D.