SKG4-E Gas Fired Humidifier
Installation Instructions and User Manual
Page | - 50 -
Menu - General
[
Level 1 - No password required]
Press the back/menu button from the Idle Screen to access the General menu
Sub-Menu
Setting
Default
Range
(
* indicates no configuration; display only)
Description/Notes
Status
Interlock:
Closed
* (Closed, Open)
Displays the status of the interlock.
If
Open
is displayed, it indicates that the humidifier is stopped as a
result of the interlock safety being open.
SupplyHighLimit:
Closed
* (Closed, Open)
Displays the status of the high limit contact.
If
Open
is displayed, it indicates that the humidity level has exceeded
the setpoint on the high limit humidistat.
AirFlow
Closed
* (Closed, Open)
Displays the status of the airflow switch.
If
Open
is displayed, it indicates that the airflow is not detected by the
air pressure switch.
OccupancyState:
Current value
* (Occupied, Unoccupied, Vacant, Off)
Displays the current occupancy state.
(Only appears if
ControlProfile
is set to an internal control mode
or
HumCntrlDemandSrc
is set to
RoomDemand
.)
HumDemand:
Current Value
* (min: 0.00%, max: 100.00%)
Displays the current humidity demand value.
ControlState:
Current Value
* (Off, Normal, LowLimit, HighLimit, Airflow,
Interlock)
Displays the current state of the safety control circuit and whether the
circuit has been disconnected due to a safety switch.
PowerOutput:
Current value
* (min: 0.00%, max: 100.00%)
Displays the measured power output of the system as a percentage of
the total power.
Module1 to 4
[3]
BoilerDemand:
Current value
* (min: 0.00%, max: 100.00%)
Displays the measured humidity demand of the humidifier module.
ServiceDue:
Off
* (Off, On)
Displays whether the humidifier module is due for servicing.
ModuleState:
Current value
* (Off, Idle, LineRinse, TankRinse, Filling, Draining,
Heating, Boiling, Alarm, PurgeAir)
Displays the current state of operation of the humidifier module.
Control
RoomDemand:
Current value
* (min: 0.00%, max: 100.00%)
Displays the room humidity demand value.
(Only appears if
ControlProfile
is set to an internal control mode
or
HumCntrlDemandSrc
is set to
RoomDemand
.)
SupplyHLDemand:
Current value
* (min: 0.00%, max: 100.00%)
Displays the supply high limit humidity demand value.
(Only appears if
ModHLProfile
is set to an internal control mode
or
HumCntrlHLSrc
is set to
SupplyHLDemand
.)
Physical IO
WtrLeakDet:
Ok
* (Ok, Leak)
Displays whether a water leak has been detected.
If
Leak
is displayed, it indicates that there is a leak within the water
line.
SupplyHLRH:
Current value
* (min: 0.00%, max: 100.00%)
Displays the supply high limit humidity reading value.
(Only appears if
ModHLProfile
is set to
InternAnalog
or
SupplyHLReadingSrc
is set to
SupplyHLRH
.)
RoomRH:
Current value
* (min: 0.00%, max: 100.00%)
Displays the room humidity reading value.
(Only appears if
ControlProfile
is set to
InternAnalog
or
RoomRHSrc
is set to
RoomRH
.)
ControlInput:
Current value
* (min: 0.00%, max: 100.00%)
Displays the current control input reading.
BinExtDemand:
0%
* (0%, 100%)
Displays whether there is currently a humidity demand, when an
On/Off humidifier is used.
(Only appears when using an On/Off humidifier.)
Interlock:
Closed
* (Closed, Open)
Displays the status of the interlock.
If
Open
is displayed, it indicates that the humidifier is stopped as a
result of the interlock safety being open.