SKG4-E Gas Fired Humidifier
Installation Instructions and User Manual
Page | - 51 -
Sub-Menu
Setting
Default
Range
(
* indicates no configuration; display only)
Description/Notes
Physical IO
SupplyHighLimit:
Closed
* (Closed, Open)
Displays the status of the high limit contact.
If
Open
is displayed, it indicates that the humidity level has exceeded
the setpoint on the high limit humidistat.
AirFlow:
Closed
* (Closed, Open)
Displays the status of the airflow switch.
If
Open
is displayed, it indicates that the airflow is not detected by the
air pressure switch.
ServiceWarnRelay:
Current value
* (Off, On)
Displays the status of the service warning relay.
AlarmWarnRelay:
Current value
* (Off, On)
Displays the status of the alarm warning relay.
PowerOutFdbck:
Current value
* (min: 0.00%, max: 100.00%)
Displays the feedback value of power output analog output.
WtrLvl1:
Current value
* (min: 0.0%, max: 120.0%)
Displays the percentage of water remaining in the evaporation
chamber for the first humidifier module.
WtrLvl2:
Current value
* (min: 0.0%, max: 120.0%)
Displays the percentage of water remaining in the evaporation
chamber for the second humidifier module.
(Only appears when there is a second humidifier module.)
WtrLvl3:
Current value
* (min: 0.0%, max: 120.0%)
Displays the percentage of water remaining in the evaporation
chamber for the third humidifier module.
(Only appears when there is a third humidifier module.)
WtrLvl4:
Current value
* (min: 0.0%, max: 120.0%)
Displays the percentage of water remaining in the evaporation
chamber for the fourth humidifier module.
(Only appears when there is a fourth humidifier module.)
Module1 to 4
[18]
ChimneyTemp1 to 4:
Current value
* (min: 0.00°C, max: 260.00°C)
Units: C, F
Displays the flue gas temperature value.
WtrTemp1 to 4:
Current value
* (min: 0.00°C, max: 125.00°C)
Units: C, F
Displays the temperature of water in the evaporation chamber.
WtrFreq:
Current value
* (0 Hz, 30000 Hz)
Displays the measured input frequency of the water level sensor.
AmbientTemp1 to 4:
Current value
* (min: -40.00°C, max: 100.00°C)
Units: C, F
Displays the temperature value inside of the weather proof enclosure.
(Only appears for units with the weather proof enclosure.)
FanFdback:
Current value
* (0Hz, 400Hz)
Displays the feedback value from the burner fan.
FanPWM:
Current value
* (0.00%, 100.00%)
Displays the strength of the PWM control signal from the burner fan.
BurnerAirInlet:
Normal
* (Normal, Blocked)
Displays the status of the burner inlet air pressure switch. If
Blocked
is
displayed, it indicates that the air pressure switch is open due to the
burner inlet being blocked.
WtrLvlLow:
Current value
* (Inactive, Active)
Displays the status of the resistive low water level sensor.
WtrLvlHigh:
Current value
* (Inactive, Active)
Displays the status of the resistive high water level sensor.
FoamSensor1 to 4:
NoFoam
* (NoFoam, Foam)
Displays whether foam has been detected within the evaporation
chamber. If
Foam
is displayed, it indicates that the Anti-Foaming
Energy Conservation (AFEC) system has detected foam. The
humidifier will drain for a few minutes and return to normal operation.
GasValve:
Current Value
* (Off, On)
Displays the status of the gas valve.
TankWtrValve:
Current value
* (Off, On)
Displays the status of the evaporation chamber water supply valve.
WtrLvlValve:
Current value
* (Off, On)
Displays the status of the water level sensor supply valve.
DrainCoolValve:
Current value
* (Off, On)
Displays the status of the internal drain cooler valve.
DrainPump:
Current value
* (Off, On)
Displays the status of the drain pump.
IgnitionCtrl:
Current Value
* (Off, On)
Displays the status of the ignition control module.
DrainValve:
On
* (On, Off)
Displays the status of the normally open drain valve.
(Only appears for units with the weather proof enclosure.)