SKG4-E Gas Fired Humidifier
Installation Instructions and User Manual
Page | - 56 -
Sub-Menu
Setting
Default
Range
(
* indicates no configuration; display only)
Description/Notes
Physical IO
RoomRHSigType:
0-10Vdc
0-10Vdc, 2-10Vdc, 4-20mA, 0-20mA
Select the signal type for the room humidity analog input.
(Only appears if
ControlProfile
is set to
InternAnalog
or
RoomRHSrc
is set to
RoomRH
.)
CntrlSigType:
0-10Vdc
0-10Vdc, 2-10Vdc, 4-20mA, 0-20mA
Select the signal type for the control demand analog input.
Module 1 to 4
[2]
WtrTemp1 to 4:
Current value
* (min: 0.00°C, max: 125.00°C)
Units: C, F
Displays the temperature of water in the evaporation chamber.
WtrTempOffset:
0.00°C
min: -10.00°C, max: 10.00°C
Units: C, F
Set a temperature offset for the evaporation chamber water temperature value, in order to
adjust the reading of the temperature sensor to the proper temperature.
Extended
Config
InstallationDate:
YYYY/MM/DD
Set the device installation date.
AlarmBuzzer:
Disabled
Normal, Disabled
Select whether to enable or disable the alarm buzzer sound whenever there is a system
warning. This will not affect the Status Display LED.
SysLogLevel:
Debug
None, Emergency, Alert, Critical, Error,
Warning, Notice, Info, Debug
Select the type of information to be stored on log file.
(The humidifier must be connected to an SD card.)
Module 1 to 4
[2]
MaxOutput:
100%
min: 10%, max: 100%
Set the maximum steam output of the humidifier module relative to its total capacity.
(The minimum value may vary based on the humidifier model.)
WtrAutoCalib1 to 4:
Always
None, Once, Always
Select the frequency of the auto calibration setting for the water level sensor.
Master [14]
BlowdownRate:
0%
min: 0%, max: 100%
Define the rate of boiler blowdown or water dilution, in order to minimize water impurities.
DrainInterval:
6hr
min: 0hr, max: 24hr
Set the frequency of the drain cycle. In general, a more frequent drain cycle is required as the
water hardness level rises. The drain cycle setting does not affect the AFEC system.
IdleTempStpnt:
0°C
min: 0°C, max: 60°C
Units: C, F
Set the idle temperature setpoint value for the evaporation chamber when there is no
demand.
IdleTime:
24hr
min: 0hr, max: 72hr
Set the amount of time the humidifier can remain in standby mode until an automatic drain
cycle is performed.
ServInterval:
1000hr
min: 100hr, max: 1000hr
Set the time of operation before the humidifier calls for servicing.
TankRinseInterval:
3day
min: 1day, max: 7day
Set the amount of time the humidifier stays in “Idle” or “Off” mode, before the evaporation
chamber undergoes an automatic rinse cycle.
MinSteamOut:
0%
min: 0%, max: 25%
Set the minimum steam production demand value, below which no steam will be produced.
DrainVolume:
100%
min: 25%, max: 100%
Define the volume of water that is drained from the chamber, relative to the total capacity of
the chamber.
NumModules:
1
min: 1, max: 4
Select the total number of active humidifier modules. This value must only be changed when
performing combustion adjustment, after which it must be set back to its initial value.
(Only applicable for units having multiple modules.)
ServOperation:
Allowed
Allowed, NotAllowed
Select whether to enable the unit to continue producing steam, even when it is due for
servicing. When set to
Allowed
, the unit will continue operating even when a service alarm is
active.
FillMode:
Pulsed
OneShot, Pulsed
Select the water filling method for the fill valve:
When set to
OneShot
, water will continuously flow.
When set to
Pulsed
, water will flow in short bursts.
TankRinse
Off
Off, On
Select whether to enable automatic rinse cycles while the humidifier is turned off.
When set to
Off
, the
TankRinseInterval
setting is disabled if the humidifier is turned off.
TankRinseIdle:
Off
Off, On
Select whether to enable automatic rinse cycles while the humidifier is in
“Idle” mode. When
set to
Off
, the
TankRinseInterval
setting is disabled if the humidifier is turned on.
SystMode:
Sequential
Parallel, Sequential, Hybrid
Select under which system operation mode the different modules will operate.
(Only applicable for units having multiple modules.)