SKG4-E Gas Fired Humidifier
Installation Instructions and User Manual
Page | - 57 -
Menu - Integration
[Level 5 - Requires level 5 password in order to access]
Sub-Menu
Setting
Default
Range
(
* indicates no configuration; display only)
Description/Notes
Network
NtwrkOption:
BACnet
BACnet, Modbus
Select whether to connect to a BACnet MS/TP or Modbus RTU
communication interface on terminal TB2 of the humidifier PCB.
Device
[4]
DeviceName:
-
Establish a name for the device.
Location:
-
Establish a designated location for the unit.
Description:
-
Establish a brief description for the unit.
DeviceInstance:
0153001 (0x000255a9)
Define the device instance value.
HTTPServer
[2]
HttpServerUnits:
Metric
Metric, Imperial
Select whether to use a metric or imperial system of units for the HTTP
server.
WebPriorityForWriting:
15
min: 1, max: 16
Set the priority level assigned for writing.
BACnetServer
[3]
For models connected to the BACnet network.
ListMode:
Integrator
Integrator, Advanced, Factory
Select the category of BACnet objects to display.
Units:
Metric
Metric, Imperial
Select whether to use a metric or imperial system of units for the BACnet
server.
Language:
English
(Language options vary based on region.)
Select the language for the BACnet server.
BACnetMSTP
[10]
For models connected to BACnet MSTP.
MaxMaster:
127
min: 1, max: 127
Configure MaxMaster value to increase network efficiency when there are
less than 127 devices on the network. For optimal efficiency, set value to the
highest MAC address in the MS/TP network.
MaxInfoFrames:
1
min: 1, max: 100
Configure the maximum number of information messages the controller may
transmit, before it must pass the token to the next controller.
AutoBaudRate:
Yes
No, Yes
Enable or disable automatic baud rate detection.
BaudRate:
38400
9600, 19200, 38400, 76800
Select the baud rate for data transfer.
MAC:
001
min: 0, max: 247
Set the MS/TP network MAC address.
RxValid:
0
*
Displays information on the received communication frames for
troubleshooting purposes.
RxInvalid:
0
*
RxLost:
0
*
Tx:
0
*
Displays information on the transmitted communication frames for
troubleshooting purposes.
TxLost:
0
*
BACnetIP
[6]
For models connected to BACnet IP.
BACnetIPPort:
47808
min: 0, max: 65535
Set the User Datagram Protocol (UDP) port number. BACnet port number is
set by default.
RxValid:
0
*
Displays information on the received communication frames for
troubleshooting purposes.
RxInvalid:
0
*
RxLost:
0
*
Tx:
0
*
Displays information on the transmitted communication frames for
troubleshooting purposes.
TxLost:
0
*
ModbusServer
[1]
For models connected to Modbus.
Units:
Metric
Metric, Imperial
Select whether to use a metric or imperial system of units for the Modbus
server.