SKG4-E Gas Fired Humidifier
Installation Instructions and User Manual
Page | - 65 -
Inspecting the Humidifier Components
Monthly Inspection
The humidifier must be inspected once a month by the operator. During the inspection, verify that:
The flue gas passageways external to the humidifier, such as the vent connector and the
chimney, are clear and free of obstructions and there is no condensate leak.
The vent connector is in place and is in a good condition without holes or excessive
corrosion.
The air filter located in the front cover is clean.
Yearly Inspection
The humidifier must be inspected once a year by skilled and qualified technical personnel. A flue gas
analyser must be used to verify the combustion quality. Verify the following during the inspection:
Combustion
Use a flue gas analyser to verify the values of O
2
, CO
2
, CO, NO, and NO
X
. These values
must lie within the values listed in the
SKG4 Combustion Field Adjustment Instructions
.
If any value is above the acceptable limit, the combustion needs to be readjusted. The
readjustment must be done by skilled and qualified technical personnel.
Refer to the
SKG4 Combustion Field Adjustment Instructions
for more details on the
combustion adjustment procedure.
Flue Passageways
Verify that the flue passageways external to the humidifier, such as the vent connector and chimney
stack, are clear and free of obstructions and that there is no condensate leak.
Vent Connector
Ensure that the vent connector is in place and is in good condition without holes or
corrosion.
Ensure that there is no fly ash accumulation at the vent connector and inside the
humidifier vent collector.
If there is accumulation of fly ashes, the burner must be disassembled by skilled and
qualified technical personnel for further inspection.
Other
Ensure that there are no obvious signs of deterioration of the humidifier.