SKG4-E Gas Fired Humidifier
Installation Instructions and User Manual
Page | - 23 -
Steam Pipe Work to Duct Connections with S.A.M.E2
Single Module Humidifier: SKG4-E0501
Steam distribution manifolds
(S.A.M.E2)
minimum length = 35" (900mm)
Ø3" (76mm)
Ø
½”
(15mm)
Min. 7° pipe slope
Min. 4" (100mm)
Insulated pipe
H
Air Duct
Static pressure
+ 2" (50mm)
Min. 2/5 H
Total length of steam conduit must not exceed 16ft (5m)
Illustration 19 - S.A.M.E2 Steam Pipe Work (SKG4-E0501)
A single Ø76mm feed pipe must be connected to two S.A.M.E2 steam manifolds with a suitable
reduction at the lowest point to allow a Ø15mm condensate drain from the main steam supply.
Single Module Humidifiers: SKG4-E0701 to SKG4-E1001
Min. 7° pipe slope
Ø3" (76mm)
ؽ"
(15mm)
Steam distribution manifolds
(S.A.M.E2)
minimum length = 35" (900mm)
Min. 4" (100mm)
Insulated pipe
H
Air Duct
Static pressure
+ 2" (50mm)
Min. 1/3 H
Total length of steam conduit must not exceed 16ft (5m)
Illustration 20 - S.A.M.E2 Steam Pipe Work (SKG4-E0701 to 1001)
A single Ø76mm feed pipe must be connected to three S.A.M.E2 steam manifolds with a suitable
reduction at the lowest point to allow a Ø15mm condensate drain from the main steam supply.