Stage 5 - Water Drain Connection
Water drain installation must conform to Local and National Codes.
Any installation work must be carried out by suitably qualified personnel.
Water Drain Specifications
Water drain temperature:
60˚C
Model
Water Drain Outlet
Connection Size
Pan Drain Outlet
Connection Size
Open Drain
Minimum Size
SKG4-E0501 to 1001
Ø22mm
Ø15mm
Ø80mm
SKG4-E1202 to 2002
Ø36mm
SKG4-E2503 to 4004
Ø50mm
Ø100mm
Water Drain Installation
Water drain outlet connection must be connected to drain pipe of sufficient size.
It is recommended to use standard copper hydraulic pipes of sufficient size.
Minimum water drain pipe gradient must be of 6.5mm per 300mm horizontal run.
No drain trap is required.
Pan drain connection must be connected to drain pipe through separated line.
SKG4
Main Drain
Pan Drain
4"
(102mm)
Open Drain
Illustration 29 - Water Drain Connections: Correct Installation