Stage 8 - Electrical Supply and Installation
CAUTION: Risk of electric shock. Disconnect the humidifier from the electric
supply before proceeding with the connection.
All work concerned with electrical installation MUST only be performed by a
qualified electrician and must conform to the procedure, regulation and local
codes.
Use copper power conductor only.
All incoming power supplies must be externally fused for over current protection.
The electrical supply must also be isolated for the purpose of emergency and servicing.
The isolator must have a contact separation of at least 3 mm.
An external over current protection and disconnect circuit breaker must be installed on the
supply, adjacent to the humidifier.
To provide strain relief to the supply cable, install a knock-out (not supplied) at the bottom of
the electrical compartment of the humidifier.
Ensure that the size of the wire conductors is appropriate for the maximum current supplied.
Ensure that the incoming power cable is secured via suitably sized cable gland.
Ensure that each terminal connection is secured firmly with a cable ferrule.
The humidifier cabinet has an uninterrupted or unbroken electrical ground. Do not use gas
piping as an electrical ground.
N
L
Ground
Illustration 38 - Power Supply Connection
Electrical Power Supply
Table 13 - SKG4 Electrical Power Supply
Model
Voltage
Standard
Weather Proof
Enclosure
Current
(A)
Current
(A)
SKG4-E0501 to 1001
230V - 1ph
3.5
3.8
SKG4-E1202 to 2002
230V - 1ph
4.5
5.8
SKG4-E2503 to 3003
230V - 1ph
6.0
7.8
SKG4-E3504 to 4004
230V - 1ph
7.5
9.5