SKG4-E Gas Fired Humidifier
Installation Instructions and User Manual
Page | - 48 -
Idle Screen
When the controller is in operation, the unit displays the following information on the Idle Screen:
Table 15 - Idle Screen Display Description
Setting
Default
Range
(
* indicates no configuration; display
only)
Description/Notes
HumDemand:
Current
value
* (min: 0.00%, max: 100.00%)
Displays the current humidity demand value.
ControlState:
Current
value
* (Off, Normal, LowLimit, HighLimit,
NoAirFlow, Interlock)
Displays the current state of the safety control circuit
and whether the circuit has been disconnected due to
a safety switch.
PowerOutput:
Current
value
* (min: 0.00%, max: 100.00%)
Displays the measured power output of the system as
a percentage of the total power.
Illustration 48 - Idle Screen Display
Menu Access
From the Idle Screen, the Main Menu can be accessed by pressing the Back/Menu button
,
enabling access to the General menu.
To view other menu options and perform configurations to the system, press Enter while on
the Idle Screen to advance to the Login Screen, where a valid password must be entered.
Four different passwords can be used, each granting access to an additional menu option
depending on the access level assigned to the provided password.
If a password of higher access is provided, all menu options accessible with the use of a
lower level password will also be unlocked.
Table 16 - Access Levels
Access
Level
Password
Menu Unlocked
Description/Notes
1
None
General
Grants access to General menu.
2
2222
User
Grants access to General and User menus.
3
3322
Service
Grants access to General, User and Service menus.
4
4433
Installation
Grants access to General, User, Service and Installation menus.
5
5544
Integration
Grants access to General, User, Service, Installation and Integration
menus.
Note: To modify or retrieve lost passwords, please contact factory.