SKG4-E Gas Fired Humidifier
Installation Instructions and User Manual
Page | - 53 -
Menu - User
[Level 2 - Requires level 2 (or higher) password in order to access]
Sub-Menu
Setting
Default
Range
Description/Notes
Command
OccupSchedule
-
00:00
Monday to Sunday
Event 1 to Event 6
Create a customized occupancy schedule with up to six events per day.
(Only appears if
ControlProfile
is set to an internal control mode or
HumCntrlDemandSrc
is set to
RoomDemand
.)
Control
RoomDemandLoop
[3]
Only appears if
ControlProfile
is set to an internal control mode or
HumCntrlDemandSrc
is set to
RoomDemand
.
RoomRHStp:
40.00%
min: 0.00%, max: 100.00%
Define the room demand setpoint value used during
Occupied
state.
(Only appears if
RoomRHStptSrc
is set to
Internal
.)
RoomRHUnocStp:
30.00%
min: 0.00%, max: 100.00%
Define the room demand setpoint value used during
Unoccupied
state.
RoomRHVacStp:
20.00%
min: 0.00%, max: 100.00%
Define the room demand setpoint value used during
Vacant
state.
SupplyHLLoop
[1]
Only appears if
ModHLProfile
is set to an internal control mode or
HumCntrlHLSrc
is set to
SupplyHLDemand
.
SupplyHLStp:
80.00%
min: 0.00%, max: 100.00%
Define the supply high limit demand setpoint value.
System
LocalDateTime:
YYYY-MM-DD
00:00:00
Configure the current date and time.
Interface
Local Display
[5]
BacklightLvl:
25%
min: 0%, max: 100%
Select the backlight level of the LCD screen.
Contrast:
5%
min: 0%, max: 30%
Select the contrast level of the LCD screen.
KeypadBuzzer:
Inactive
Inactive, Active
Select whether to enable or disable the key press sound.
Language:
English
(Language options vary based on region.)
Select the device language.
Units:
Imperial
Metric, Imperial
Select whether to use a metric or imperial system of units for the local
device.
HRL
[3]
For units connected to the HRL24 controller.
Temperature:
Current value
*min: -40.00°F, max: 500.00°F
[min: -40.00°C, max: 260.00°C]
Units: C, F
Displays the room temperature value measured by the HRL24 controller.
Humidity:
Current value
*(min: 0.0%, 100.0%)
Displays the room humidity value measured by the HRL24 controller.
LockSetpnt:
Unlock
(Unlock, lock)
Displays whether the setpoint obtained from the HRL24 controller can be
modified or not.