SKG4-E Gas Fired Humidifier
Installation Instructions and User Manual
Page | - 55 -
Menu - Installation
[Level 4 - Requires level 4 (or higher) password in order to access]
Sub-Menu
Setting
Default
Range
(
* indicates no configuration; display only)
Description/Notes
Quick Config
BlowdownRate:
0%
min: 0%, max: 100%
Define the rate of boiler blowdown or water dilution, in order to minimize water impurities.
DrainInterval:
6hr
min: 0hr, max: 24hr
Set the frequency of the drain cycle. In general, a more frequent drain cycle is required as the
water hardness level rises. The drain cycle setting does not affect the AFEC system.
IdleTime:
24hr
min: 0hr, max: 72hr
Set the amount of time the humidifier can remain in standby mode until an automatic drain
cycle is performed.
ServInterval:
1000hr
min: 1000hr, max: 3000hr
Set the time of operation before the humidifier calls for servicing.
DrainVolume
100%
min: 25%, max: 100%
Define the volume of water that is drained from the chamber, relative to the total capacity of
the chamber.
ServOperation:
Allowed
Allowed, NotAllowed
Select whether to enable the unit to continue producing steam, even when it is due for
servicing. When set to
Allowed
, the unit will continue operating even when a service alarm is
active.
FillMode:
Pulsed
OneShot, Pulsed
Select the water filling method for the fill valve:
When set to
OneShot
, water will continuously flow.
When set to
Pulsed
, water will flow in short bursts.
Control
ControlProfile:
ExternAnalog
ExternAnalog, ExternNetwork, InternAnalog,
InternNetwork, HRL, Custom
Select a preconfigured control mode profile for the modulating humidity demand. Select the
Custom
option to configure individual settings.
(Network option only applicable for BACnet models.)
ModHLProfile:
Disabled
Disabled, ExternAnalog, ExternNetwork,
InternAnalog, InternNetwork, Custom
Select a preconfigured control mode profile for the modulating high limit demand. Select the
Custom
option to configure individual settings.
(Network option only applicable for BACnet models.)
RoomDemandLoop
[2]
Only appears if
ControlProfile
is set to an internal control mode or
HumCntrlDemandSrc
is set to
RoomDemand
.
RoomRHSrc:
None
None, RoomRH, Network
Select the reading source for the room demand.
(Network option only applicable for BACnet models.)
RoomRHStptSrc:
None
None, Internal, ControlInput
Select the room demand setpoint source.
SupplyHLLoop
[2]
Only appears if
ModHLProfile
is set to an internal control mode or
HumCntrlHLSrc
is
set to
SupplyHLDemand
.
SupplyHLReadingSrc:
None
None, SupplyHLRH, Network
Select the reading source for the supply high limit demand.
(Network option only applicable for BACnet models.)
SupplyHLStpntSrc:
None
None, Internal, ControlInput
Select the supply high limit demand setpoint source.
HumidityControl
[4]
HumLowDeadBand:
1.00%
min: 0.00%, max: 100.00%
Set the lower limit deadband value for the humidity demand.
HumCntrlDemandSrc:
ControlInput
None, ControlInput, RoomDemand, Network
Select the humidity control demand source for modulating humidifiers.
(Network option only applicable for BACnet models.)
HumCntrlHLSrc:
None
None, ControlInput, SupplyHLDemand,
Network
Select the humidity control high limit source for modulating humidifiers.
(Network option only applicable for BACnet models.)
HumCntrlBinDemandSrc:
None
None, BinaryExtDemand
Select the humidity control demand source for On/Off humidifiers.
Physical IO
AlwaysRoomRH:
Off
Off, On
Select whether to always display the
RoomRHSigType
setting, regardless of the configuration
selected in the
ControlProfile
setting.
AlwaysSupplyRH:
Off
Off, On
Select whether to always display the
SupplyRHSigType
setting, regardless of the
configuration selected in the
ModHLProfile
setting.
SupplyRHSigType:
0-10Vdc
0-10Vdc, 2-10Vdc, 4-20mA, 0-20mA
Select the signal type for the duct or supply high limit humidity analog input.
(Only appears if
ModHLProfile
is set to
InternAnalog
or
SupplyHLReadingSrc
is set to
SupplyHLRH
.)