SKG4-N Gas Fired Humidifier 

Start-up Check List 

 

SKG4-N Start-up Check List - 180807

 

www.neptronic.com

 

 

2/2

 

Start-Up 

Start-up 

1.  Proceed to start-up the humidifier, as follows: 

 

a)  With the humidifier front access open, ensure that the manual drain valve is 

closed. 

 

b)  Turn on the humidifier by pressing and holding the Power button 

 for 3 

seconds. Verify that the controller Status Display LED is blue. 

 

c)  Verify that there is a humidity demand displayed on the LCD screen of the 

humidifier. 

 

d)  Ensure that the water supply valve connected to the humidifier is turned on 

and that water is flowing directly to the humidifier water supply inlet. Ensure 
that the water shut off valve is turned off. 

 

e)  Verify the water level as water is filling the evaporation chamber by using the 

control panel to access the 

WaterLevel

 setting located in the 

Physical IO

 sub-

menu of the 

General

 menu. Ensure that there are no water leaks along the 

water line. 

 

f)  If there is a humidity demand, the burner combustion blower(s) will start, and 

after approximately 90 seconds the combustion will start. From a cold water 
start, the humidifier will require 5 to 10 minutes to produce steam. 
The humidifier controller will indicate the water temperature and flue gas 
temperature. 

 

g)  During normal operation while steam is produced, the water temperature 

must be 212 

˚F (100˚C) and the flue gas temperature must be around 248 to 

392

˚F (120 to 200˚C). The water level percentage must not indicate less than 

95%. 

 

h)  Once the evaporation chamber has been filled, observe for water, steam and 

flue gas leaks during several minutes of operation. 

 

Combustion Field 

Adjustment 

2.  Please refer to the 

SKG4 Combustion Field Adjustment Instructions

 enclosed in 

this package to perform this operation. 

 

Safety Test 

3.  Check  the  location  of  the  Airflow  switch  in  the  system  and  its  operation  by 

stopping the fan. With no air movement, the humidifier should automatically stop. 

 

Drain and Reset 

4.  Turn  off  the  humidifier  by  pressing  and  holding  the  Power 

  button  for  3 

seconds. 

 

5.  Conduct  a  drain  cycle  by  pressing  and  holding  the  Drain  button 

  for  3 

seconds. Ensure that the evaporation chamber has been emptied. 

 

6.  Once the drain cycle is complete, restart the humidifier by pressing and holding 

the Power 

 button for 3 seconds. 

 

7.  Reset the Airflow switch if needed. 

 

End 

8.  The humidifier is now ready for normal operation. 

 

 

Controls 

14.  Ensure that the Interlock is properly connected to the printed circuit board. If the 

Interlock  is  not  used,  verify  that  a  jumper  is  connected  between  terminals  TB3 
1&4. 

 

15.  If  a  room  or  duct  humidistat  is  used,  verify  that  it  is  correctly  installed  and 

properly  connected  to  the  humidifier.  Verify  that  the  setpoints  are  properly 
adjusted. 

16.  Turn the power on using the circuit breaker.                                      
17.  Confirm  the  control  set-up  of  the  humidifier  and  verify  that  the  setpoints  are 

properly adjusted. 

 

 

 

 

 

 