SKGE3 Gas Fired Humidifier
Installation Instructions and User Manual
19
Stage 2
– Steam Distribution Installation
Multi-Steam Configurations
Single Module
Humidifiers:
SKGE3-0501
SKGE3-0701
SKGE3-0801
SKGE3-1001
Steam pipe work SKGE3-0501 to 1001 - Fig. 26
A single Ø76mm feed pipe must be connected to a single Multi-Steam with a suitable
reduction at the lowest point to allow a Ø15mm condensate drain from the main
steam supply.
2 Modules
Humidifiers:
SKGE3-1202
SKGE3-1502
SKGE3-1702
SKGE3-2002
Steam pipe work SKGE3-1202 to 2002 - Fig. 27
Two Ø76mm steam outlets to a single Ø108mm feed pipe must be connected to a
single Multi-Steam with a suitable reduction at the lowest point to allow a Ø15mm
condensate drain from the main steam supply.
Ø76mm
Ø15mm
Min. 7° pipe slope
Min. 50mm
Insulated pipe
Air Duct
Static pressure
+ 50mm
Total length of steam conduit should not exceed 5 meters.
Multi-Steam
Min. 50mm
Min. 50mm
min
7° p
ipe s
lope
Ø76mm
Ø76mm
Ø108mm
Ø15mm
Min. 7° pipe slope
Static pressure
+ 50mm
Insulated pipe
Air Duct
Total length of steam conduit should
not exceed 5 meters.