Stage 2
– Steam Distribution Installation
3 Modules
Humidifiers:
SKGE3-2503
SKGE3-2703
SKGE3-3003
Steam pipe work SKGE3-2503 to 3003 - Fig. 28
Three Ø76mm steam outlets to a single Ø133mm feed pipe must be connected to a
double Multi-Steam with a suitable reduction at the lowest point to allow a Ø15mm
condensate drain from the main steam supply.
If these Ø15mm condensate pipes are connected, the common condensate drain
must be Ø22mm.
4 Modules
Humidifiers:
SKGE3-3504
SKGE3-3704
SKGE3-4004
Steam pipe work SKGE3-3504 to 4004 - Fig. 29
Two Ø76mm steam outlets to a single Ø108mm feed pipe must be connected to a
single Multi-Steam with a suitable reduction at the lowest point to allow a Ø15mm
condensate drain from the main steam supply.
This must be reproduced two times.
If the two Ø15mm condensate pipes are connected, the common condensate drain
must be Ø22mm.
Ø22mm
Ø76mm (x3)
Ø133mm
Min. 7° pipe slope
Insulated pipe
Air Duct
Ø15mm
Static pressure
+ 50mm
min
7° p
ipe s
lope
Total length of steam conduit
should not exceed 5 meters.
min
7° p
ipe s
lope
Ø15mm
Static pressure
+ 50mm
Ø22mm
Min. 7° pipe slope
Insulated pipe
Air Duct
Ø76mm
(x2)
Ø108mm
x2
Total length of steam conduit
should not exceed 5 meters.