SKGE3 Gas Fired Humidifier
Installation Instructions and User Manual
22
Stage 4 – Water Supply Installation
Water supply installation must conform to local codes and regulations.
Any installation work must be carried out by suitably qualified personnel.
Water Inlet
Specifications
The Neptronic® SKGE3 Humidifier is designed to be used with tap, reverse osmosis,
deionised and de-mineralized water.
Maximum water supply pressure: 70 to 480kPa (0.7 to 4.8 bar).
Minimum water temperature: +4
˚C
Maximum water temperature: +40
˚C
Model
Water inlet
Connection size
SKGE3-
0501, 0701, 0801, 1001
1202, 1502, 1702, 2002
2503, 2703, 3003
3504, 3704, 4004
1/2
’’ BSPT
Male
Water Supply
Line Installation
To facilitate servicing, a shut off valve (not supplied) must be installed in the water
line, within 1 meter of the humidifier.
It is recommended to install a water hammer arrestor, in order to absorb hydraulic
shock and minimize water hammer when the fill valve closes.
Water supply connection - Fig. 31
Double Check
Valve
In order to comply with WRAS (Water Regulations Advisory Scheme) regulations in
force in the United Kingdom, a double check valve must be installed as indicated in
the above figure.
All connections must be made using the gaskets provided. On the inlet side of the
check valve shown is a compression fitting for a 15mm pipe.
!