SKGE3 Gas Fired Humidifier
Installation Instructions and User Manual
23
Stage 5 – Water Drain Connection
Water drain installation must conform to local codes and regulations.
Any installation work must be carried out by suitably qualified personnel.
Water Drain
Specification
Water drain temperature: +60
˚C
Model
Water Drain Outlet
Connection size
SKGE3-
0501, 0701, 0801, 1001
1202, 1502, 1702, 2002
2503, 2703, 3003
3504, 3704, 4004
Ø 38mm (1-
1/2’’)
(BS2871 spigot)
Water Drain
Installation
Water drain outlet connection must be connected to drain pipe of sufficient size.
It is recommended to use Ø38mm minimum standard copper hydraulic pipes.
Minimum water drain pipe gradient must be 1.5mm in 1000mm horizontal run.
No drain trap is required.
Drain connection - Fig. 32
Pan Drain
Connection on
Weather Proof
Enclosure
The weather proof enclosure is provided with a pan drain at the base of the SKGE3
humidifier.
Weather proof enclosure base pan drain outlet dimension (in mm). - Fig. 33
Weather Proof
Enclosure
Water Drain Valve
The weather proof enclosure is equipped with a normally open valve, enabling the
humidifier to drain all water during a power failure, in order to prevent water from
freezing within the unit. During normal operation, the humidifier reduces drain water
temperature to +60°C.
CAUTION:
During a power failure, the drain water temperature is not reduced.
Installed drain piping must be rated to +100°C.
!
S K G E 3
1 0 0 m m
Ø 4 0 m m
m in im u m
M a in D ra in
P a n d ra in
61
0
30
5
1/2
xU
U
Pan drain outlet
Ø 15mm