SKGE3 Gas Fired Humidifier
Installation Instructions and User Manual
47
Com Port Set-up Menu
Display
Description
Values
Com Port Speed:
N/A Baud
Not Applicable, communication speed unit is not a variable.
The communication speed is expressed in Baud.
Default: N/A
MS/TP MAC Address
Selection of MS/TP MAC address
This value is locked, in order to avoid incorrect set-up of the
MAC Address.
To unlock the setting, put the BACnet
®
interface dip switch
No1 at the ON position (Configuration mode),
see the
‘’Stage 9 – BACnet
®
Interface Set-
up’’ section of the
manual.
From 0 to 255
Increment: 1
Default: 0
Device Instance
Selection of device instance value.
This value is locked, in order to avoid incorrect set-up of the
device instance.
To unlock the setting, put the BACnet
®
interface dip switch
No1 at the ON position (Configuration mode),
see the
‘’Stage 9 – BACnet
®
Interface Set-
up’’ section of the
manual.
From 0 to 4194303
Increment: 1
Default: 01530000
COM PORT SET UP
600
Com Port Speed
N/A Baud
COM PORT SET UP
601
MS/TP MAC Address
255
Value is locked !
COM PORT SET UP
602
Device Instance
01530000
Value is locked !
All manuals and user guides at all-guides.com