SKGE3 Gas Fired Humidifier
Installation Instructions and User Manual
5
Technical Specifications
General overview -
Fig.1
Model
No of
Modules
Steam
capacity
(kg/hr)
Natural Gas
Propane Gas
Current
at 230V
(Amp)
Multi-Steam
header
diameter
(mm)
Input
(kW)
Consumption
(m
3
/h)
Input
(kW)
Consumption
(m
3
/h)
SKGE3-0501 N/P
1
50
49
4.6
55
2.1
3.5
76
SKGE3-0701 N/P
1
70
62
5.8
68
2.6
3.5
76
SKGE3-0801 N/P
1
80
69
6.5
75
2.9
3.5
76
SKGE3-1001 N/P
1
100
72
6.8
79
3.0
3.5
76
SKGE3-1202 N/P
2
120
110
10.4
123
4.8
4.5
76
SKGE3-1502 N/P
2
150
123
11.6
136
5.2
4.5
100
SKGE3-1702 N/P
2
170
134
12.6
147
5.7
4.5
100
SKGE3-2002 N/P
2
200
144
13.6
158
6.1
4.5
100
SKGE3-2503 N/P
3
250
203
19.1
222
8.6
6.0
100
SKGE3-2703 N/P
3
270
206
19.4
225
8.7
6.0
100
SKGE3-3003 N/P
3
300
216
20.4
236
9.1
6.0
100
SKGE3 3504 N/P
4
350
275
25.9
301
11.6
7.5
100
SKGE3-3704 N/P
4
370
278
26.2
304
11.8
7.5
100
SKGE3-4004 N/P
4
400
288
27.2
315
12.2
7.5
100
Notes
: 1 - Maximum static duct pressure is 1.250 kPa. For higher static duct pressures, consult Neptronic or its authorized
distributor.
2 - Standard humidifier is designed for n
atural ventilation combustion air, ‘’Ducted Combustion Air’’ option is
available upon request, see stage 6 of installation.
All manuals and user guides at all-guides.com