SKR Humidifier – kit N
User Manual
www.neptronic.com
9
6.2.
Drain connections
IMPORTANT: No external drain traps are required.
Drain outlet specification:
Main drain 1/2” (13mm) standard copper (evaporation chamber).
Pan drain 1/2” (13mm) standard copper.
Water drain temperature: 140°F (60
C).
Two pipes
minimum 1” (25mm)
(by others) must be inserted over the humidifier outlet pipes
(fig.10). This will create a critical air gap at the drain connections.
NOTE
: This air gap is critical for normal drain siphon operation.
(Fig. 10a)
Correct installation
(Fig. 10b)
Incorrect installation