SKR Humidifier – kit N
User Manual
www.neptronic.com
8
6.
Plumbing connections
The
SKR
humidifier can operate with soft or hard water. Therefore, for normal operation, no pre-treatment of
water is necessary.
IMPORTANT:
Plumbing installation should conform to Local and National Codes.
6.1.
Water supply
Water inlet specifications:
IMPORTANT: Risk of malfunction, do not use demineralized water.
Inlet water pressure: 15 to 70 psig (1 to 4,8 bars)
IMPORTANT: Risk of malfunction. Do not reduce water supply flow.
Maximum temperature: 85°F (30
C)
3/8'' (10mm) standard copper supply water connection
To facilitate servicing, a shut off valve (not supplied) should be installed in the water supply line, close to
the humidifier.
It is recommended to install a standard strainer in the water supply line.
If required, an air chamber made of copper pipe (see fig. 9) will absorb hydraulic shock, avoiding water
hammer, when the fill valve closes. There are other standard types of air chambers commercially
available.
Please follow the steps below:
1.
Connect 3/8'' (10mm) copper pipe to the 3/8'' (10mm) braided hose (supplied).
2.
Hand tighten the swivel top 3/4'' (20mm) fitting to the male threaded valve connection.
IMPORTANT: Risk of damage to the valve, do not use wrench to tighten swivel.