SKS4 Steam to Steam Humidifier 

Start-up Check List 

 

SKS4-CE Start-up Check List - 180717

 

www.neptronic.com

 

1/2

 

Start-up Procedure 

 

Initial verification and start-up must be carried out by suitably qualified personnel. 

It  is  strictly  recommended  to  follow  this  start-up  procedure  in  order  to  avoid  any  anomaly  resulting 
from inaccurate installation of the components. 

Initial Verification 

Clearance 

1.  Ensure that the humidifier cabinet is installed in a location in which 

the humidifier can be serviced correctly. 

 

Electrical 

Supply 

2.  Verify  that  the  power  supply  (voltage)  conforms  to  the  appliance 

name plate on the side of the humidifier. 

 

3.  Confirm  that  24Vac  is  present  between  terminals  TB4  1&2  on  the 

printed circuit board. 

 

Water Supply 

4.  Ensure  that  water  is  supplied  to  the  humidifier  and  that  a  shutoff 

valve is placed outside the humidifier. 

 

5.  With  the  water  shutoff  valve  turned  on,  check  that  the  drain 

connections  are  connected  to  the  main  drain  line  with  sufficient 
diameter. Ensure that there are no apparent leaks. 

 

6.  Confirm that the drain piping is properly connected with a pitch of at 

least 6.5mm per 300mm. 

 

Clean Steam 

7.  Verify  that  the  steam  distributors  are  properly  installed  into  the 

ventilation duct. 

 

8.  Verify  that  the  flexible  steam  hoses  and  rigid  steam  supply  pipes 

are  shorter  than  5  m  in  total,  are  properly  sloped  and  have 
condensation “S” traps wherever required. 

 

Raw Steam or  
HTHW Supply 

9.  Confirm  that  raw  steam  or HTHW is  supplied  to the  humidifier  and 

that the supply line is hot upstream the control valve. The pressure 
must not exceed 15 PSI (103.4 kPa) for SLP models. 

 

10.  Confirm  that  the  shut-off  valve  located  outside  the  humidifier  is 

closed. With the shut-off valve turned on, check for leaks or hissing 
sounds. 

 

11.  When  using  raw  steam  supply,  verify  the  type  and  size  of  the 

condensate return steam trap. The steam trap must be of float type 
and of sufficient dimension, according to the capacity. 

 

Controls 

12.  Ensure  that  the  control  valve  is  properly  connected  to  the  output 

control signal of the humidifier. 

 

13.  Ensure that the Airflow switch is properly installed and connected to 

the printed circuit board. If an Airflow switch is not used,  verify that 
a jumper is connected between terminals TB3 1&2. 

 

14.  Ensure  that  the  High  limit  duct  humidistat  is  properly  installed  and 

connected  to  the  printed  circuit  board.  Verify  that  the  setpoint  is 
properly  adjusted.  If  a  High  limit  duct  humidistat  is  not used,  verify 
that a jumper is connected between terminals TB3 1&3. 

 

15.  Ensure that the Interlock is properly connected to the printed circuit 

board. If the Interlock is not used, verify that a jumper is connected 
between terminals TB3 1&4. 

 

16.  If  a  room  or  duct  humidistat  is  used,  verify  that  it  is  correctly 

installed  and  properly  connected  to  the  humidifier.  Verify  that  the 
setpoints are properly adjusted. 

 

17.  Turn the power on using the disconnect switch or circuit breaker. 

 

18.  Confirm  the  control  set-up  of  the  humidifier  and  verify  that  the 

setpoints are properly adjusted. 

 