SKS4 Steam to Steam Humidifier 

Start-up Check List 

 

SKS4-CE Start-up Check List - 180717

 

www.neptronic.com

 

2/2

 

Start-Up 

Start-up 

1.  Proceed to start-up the humidifier, as follows: 

 

a)  Turn on the humidifier by pressing and holding the Power button 

 for 3 seconds. Verify that the controller Status Display LED is 

blue. 

 

b)  Verify  that  there  is  a  humidity  demand  displayed  on  the  LCD 

screen of the humidifier.  

 

c)  Ensure  that  the  water  supply  valve  connected  to  the  humidifier 

is  turned  on  and  that  water  is  flowing  directly  to  the  humidifier 
water supply inlet. Ensure that the water shut off valve is turned 
off. 

 

d)  Verify the water level as water is filling the evaporation chamber 

by  using  the  control  panel  to  access  the 

WaterLevel

  setting 

located  in  the 

Physical  IO

  sub-menu  of  the 

General

  menu. 

Ensure that there are no water leaks along the water line. 

 

e)  Once  the  evaporation  chamber  has  been  filled,  observe  the 

system  for  water  and  steam  leaks  during  several  minutes  of 
operation. 

 

Safety Test 

2.  Check  the  location  of  the  Airflow  switch  in  the  system  and  its 

operation by stopping the fan. With no air movement, the humidifier 
should automatically stop. 

 

Drain and 

Reset 

3.  Turn off the humidifier by pressing and holding the Power 

 button 

for 3 seconds. 

 

4.  Conduct a drain cycle by pressing and holding the Drain button 

 

for  3  seconds.  Ensure  that  the  evaporation  chamber  has  been 
emptied. 

 

5.  Once the drain cycle is complete, restart the humidifier by pressing 

and holding the Power 

 button for 3 seconds. 

 

6.  Reset the Airflow switch if needed. 

 

End 

7.  The humidifier is now ready for normal operation. 

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 