Evaporative Cooling Humidifier
Installation Instructions and User Manual
www.neptronic.com
Page | 18
Main Menu - System Setup
Sub-Menu
Settings
Default
Range
Notes/Conditions
2A) Clock
Time Format:
12h
12h (AM/PM) or 24h
Actual Time:
00.00
0 to 24 hours
Date:
13:09:03
YY/MM/DD
UTC diff:
+4h
-12 to +14 hours
Daylight Saving:
Off
On (Enable), Off (Disable)
2B) Drain Schedule
Drain schedule
disabled
n/a n/a
The drain schedule is only available for Recirculation models with
the
Auto Drain (step 4C)
set to
Schedule
in the Installer menu. The
drain schedule is not available for Direct Feed models
Day:
Monday
Monday to Sunday
Each day of the week can have different events; up to 4 events
each. The events displayed are configured and apply to the day
that’s displayed.
If you select
Wait
,
Start Drain
, or
Stop Drain
, a clock setting is
displayed. Set the time/duration at/in which the unit can perform
the drain task. An event cannot cross-over midnight, see Note 2 on
page 16.
Wait
= time before drain sequence can start.
Start Drain = time at which drain sequence will start.
Stop Drain = time at which drain sequence will stop.
Event 1:
Unused
Unused, Wait, Start Drain, Stop Drain | 00:00 to 23:59
Event 2:
Unused
Unused, Wait, Start Drain, Stop Drain | 00:00 to 23:59
Event 3:
Unused
Unused, Wait, Start Drain, Stop Drain | 00:00 to 23:59
Event 4:
Unused
Unused, Wait, Start Drain, Stop Drain | 00:00 to 23:59
2C) Occ.Schedule
Occupancy schedule
disabled
n/a
n/a
The drain schedule is only available when the Occupancy
Schedule
(step 4B) is
set to
ON
in the Installer menu.
Day:
Monday
Monday to Sunday
Each day of the week can have different events; up to 4 events
each. The events displayed are configured and apply to the day
that’s displayed.
If you select
Occup.
,
Unoccup.
,
Vacancy
or
Off
, a clock setting is
displayed. Set the time/duration at/in which the unit can perform
the drain task. An event cannot cross-over midnight, see Note 2 on
page 16.
Occup.
= duration the unit remains in Occupancy mode.
Unoccup. = duration the unit remains in Unoccupied mode.
Vacancy = duration the unit remains in Vacancy mode.
Off
= duration the unit remains Off.
Event 1:
Unused
Unused, Occup., Unoccup, Vacancy, Off | 00:00 to 23:59
Event 2:
Unused
Unused, Occup., Unoccup, Vacancy, Off | 00:00 to 23:59
Event 3:
Unused
Unused, Occup., Unoccup, Vacancy, Off | 00:00 to 23:59
Event 4:
Unused
Unused, Occup., Unoccup, Vacancy, Off | 00:00 to 23:59
2D) Measure
Temp Units:
° F
°C or °F
Flow Display:
Mass Flow
% or Mass Flow
Mass Flow Units:
lb/h
kg/h or lb/h
2E) Options
Setup Password:
Off
On (Enable), Off (Disable)
If enabled, the System Menu password is
372
.
Alarm Beep:
On
On (Enable), Off (Disable)
Key Press Beep:
On
On (Enable), Off (Disable)
Contrast:
5
0 to 10
Language:
English
English or Français