Evaporative Cooling Humidifier
Installation Instructions and User Manual
www.neptronic.com
Page | 19
Main Menu - Diagnostics
Sub-Menu
Settings
Default
Range
(
* indicates no configuration; display only)
Notes/Conditions
3A) Functions
Reset Alarm:
No
Yes or No
Set to
Yes
to reset any alarms that have been restored and require
a manual reset. Refer to Alarms on page 23.
Start Drain Cycle:
No
Yes or No
Set to
Yes
to start the drain sequence. The time required varies
depending on various factors, such as size of tank, quality of drain
and factory setting of drain completion time. “In Progress” is
displayed until the cycle is completed.
Disinfection Time:
15 min
15 to 30 minutes
Set to
Yes
to start the disinfection sequence. The sequence fills
the tank, and then runs the module(s) at 100% for the duration of
the selected
Disinfection Time
. It then performs an auto-drain
sequence and returns to normal operation. If during the
Disinfection Time
, the tank needs to be filled again, the timer will
stop until the tank is filled.
Start Disinfect.
No
Yes or No
3B) Cleaning
Cleaning Due On:
YY-MM-DD
*
The date represents 3 to 12 months after setting “Cleaning Done?”
to
Yes
. This “Cleaning Interval” is set by the Installer at step 4A in
the Installer menu. A “Service Warning” appears 100 hours before
the due date. A “Service Alarm” appears on the due date.
Last Cleaning:
YY-MM-DD
*
Displays the date at which the “Cleaning Done?” was set to
Yes
.
Cleaning Done?
No
Yes or No
When the unit has been cleaned, set this value to Yes to reset the
“Cleaning Due On” date and “Last Cleaning” date.
Total Runtime
0000 h
*
Displays total number of hours the unit is in function.
3C) Service
Last Silver Ion
YY-MM-DD
*
Displays the date at which the “Silv. Ion Changed” was set to
Yes
.
Silv. Ion Changed?
No
Yes or No
When the Silver Ion cartridge has been changed, set this value to
Yes
to reset the “Last Silver Ion?” date. The due date is variable
based on water flow and time in use. A “Service Alarm” appears on
the due date.
UV Lamp Due On:
YY-MM-DD
*
The date represents 1500 to 3000 hours after setting “UV Lamp
Changed?” to
Yes
. The “UV Lamp Notice” (no. of hours) is set by
the Installer at step 4A in the Installer menu. A “Service Alarm”
appears on the due date.
Last UV Lamp:
YY-MM-DD
*
Displays the date at which the “UV Lamp Changed?” was set to
Yes
.
UV Lamp Changed?
No
Yes or No
When the UV lamp has been changed, set this value to
Yes
to
reset the “UV Lamp Due On” date and “Last UV Lamp” date.
3D) Inputs
Control Mode:
Current value
*
(Int.RH, Int. Temp, Network, Ext.AI1, Ext.AI2, Ext.AI)
Setpnt Source:
Current value
*
(Internal, Network, Ext.AI1, Ext.AI2, Ext.AI3)
High Limit Src:
Current value
*
(AI1, AI2, AI3, Network, None)
Setpnt :
Current value
*
(mV)
If
External
(Ext.AI1, Ext.AI2, Ext.AI3) at step 1A “Setpnt Source”.
Demand:
Current value
*
(mV)
If
External
(Ext.AI1, Ext.AI2, Ext.AI3) at step 1A “Control Mode”.
Room Temp:
Current value
*
(mV)
If
External
(Ext.AI1, Ext.AI2, Ext.AI3) at step 1A “Room Temp Src”.
Room Humidity:
Current value
*
(mV)
If
External
(Ext.AI1, Ext.AI2, Ext.AI3) at step 1A “Room RH Src”.
High Limit Sensor:
Current value
*
(mV)
If
External
(Ext.AI1, Ext.AI2, Ext.AI3) at step 1A “High Limit Src”.
Demand:
Current value
*
(Opened or Closed)