Evaporative Cooling Humidifier
Installation Instructions and User Manual
www.neptronic.com
Page | 24
Servicing and Maintenance
This humidifier must be installed, operated, and maintained by suitably qualified personnel and in
accordance with this manual.
Preventative Maintenance
The SKV Evaporative Cooling Humidifier requires both inspection and service at regular intervals. The frequency of
servicing depends on factors such as water quality, capacity and the number of hours in operation. It is recommended to
inspect and service the evaporation module after 200 hours post commissioning. This inspection is necessary to
determine the frequency of both inspection and service.
Verification List
Perform the following activities regularly to ensure optimal performance and operation of the evaporative module(s).
Check for water leaks.
Check for stagnant water.
Observe the operation of the water flow and evaporation cycle.
Check drain operation and flow.
Ensure that all electrical connections are secure.
Ensure that the 5µ water PP pre-filter is not clogged.
Verify if the Silver Ion “service warning” has appeared. If so, replace the Silver Ion dosing cartridge
Ensure that the air duct filter upstream of the SKV evaporation module is clean.
Check for any accumulation of dirt in the bottom of the tray. If there is a significant presence of impurities,
clean the tank at the bottom of the unit.
Check the flow control at the output of the pump and clean or replace if necessary.
Ensure that the water supply hoses at the top of the evaporation module are clean and in good condition.
Remove the water distribution trays at the top of the evaporation module and make sure they are clean, clean
if necessary.
Remove the cassette containing the media and remove / clean any residue or deposits accumulated on the
media or frames.
Water Sampling and Testing (Hygiene)
Legionella disease can be fatal. Maintain and control the water system of SKV Evaporative Cooling
Humidifier according to the local Health & Safety regulation codes.
SKV Evaporative Cooling Humidifier has been designed to minimise any possible risk of Legionellosis growth. However,
perform the following checks in order to reduce the growth of Legionellosis:
Conduct a risk assessment of the water system by a competent authority.
Implement appropriate inspection and control measures.
Maintain water temperature below 68°F [20°C].
Maintain a clean, drinking quality water supply.
Avoid
water
stagnation.
Carry out regular microbiological testing of water (counting the number of bacterial units).
Refer to the ISO 5667-1 standard (Water quality - Sampling - Part 1: Guidelines for the design of programs
and sampling techniques)
Clean and disinfect the system regularly. Refer to Legionella and the prevention of legionellosis, by World
Health Organization 2007, ISBN 92 4 156297 8 for more detailed advice on control measures.
Apply disinfection measures based on the results of visual inspection and microbiological tests.