Evaporative Cooling Humidifier
Installation Instructions and User Manual
www.neptronic.com
Page | 3
Specifications
Table 2 - Water Supply and Drain Connection Specifications
Specification
Description
Water Supply Size
Ø3/4’’ (20mm) garden hose, male
Maximum Water Supply Pressure
70 PSI (4.8bar)
Maximum Water Supply Temperature
68°F (20°C)
Drain Pump Inlet Size
Ø3/4" (20mm)
Overflow Outlet Size
Tank size less than 94” (239cm):
Ø1.5" (3.8cm)
Tank size greater than 94” (239cm):
Ø2.0" (5.1cm)
Table 3 - Evaporation Module Specifications
Specification
Description
Evaporation Module Frame Material
Stainless Steel Grade 304
Evaporation Media – Material
Glass fibre material bonded with a special inorganic compound
Evaporation Media – Fire Rating
European Fire rating: (EN13501-1 & EN13238): Euro class A2, s2, d0
North America Fire rating: UL900 class 1 (by ETL)
Evaporation Media – Hygiene Evaluation
EN ISO 846, VDI6022 Part I, suitable for use in HVAC-systems (by ILH Berlin)
Dimensions and Weights
Illustration 3 - Dimensions and Weights
Evaporative Module dimensions are calculated and customized to the actual size of the duct dimension using
Humidisoft. Please refer to drawing attached and referenced with the Humidisoft project number for dimensions
and weights for your SKV.
A
B
C