background image

- 5 -

Section III Installation

Site

The indentations on the unit's sides are designed to function as handles. Lift

the unit by the handles and locate it on a sturdy work area. Ambient tempera-

tures should be inside the range of +50°F to +80°F (+10°C to +27°C).

Never place the unit in a location where excessive heat, moisture, or

corrosive materials are present.

The unit has an air-cooled refrigeration system. Air is drawn through the

front panel and discharged through the rear panel. The unit must be

positioned so the air intake and discharge are not impeded. A minimum

clearance of 12 inches (30 centimeters) at the front and rear of the unit is

necessary for adequate ventilation. Inadequate ventilation will reduce

cooling capacity and, in extreme cases, can cause compressor failure.

Excessively dusty areas should be avoided and a periodic cleaning schedule

should be instituted (see Section VI, Cleaning).

The unit will retain its full rated capacity in ambient temperatures up to

approxi75°F (+24°C). Above +75°F, derate the cooling capacity 1%

for every 1°F above +75°F, to a maximum ambient temperature of +95°F.

In terms of Celsius, derate the cooling capacity 1% for every 0.5°C above

+24°C, to a maximum ambient temperature of +35°C.

Electrical

Requirements

Line voltage may be easily accessible inside the pump/control box.

Always unplug the unit prior to removing pump/control box cover.

Refer to the serial number label on the rear of the unit to identify the specific

electrical requirements of your unit.

Ensure the voltage of the power source meets the specified voltage, ±10%.

The unit construction provides extra protection against the risk of electric

shock by grounding appropriate metal parts. The extra protection may not

function unless the power cord is connected to a properly grounded outlet. It

is the user's responsibility to assure a proper ground connection is provided.

For 220 - 240 volt units supplied without a line cord, use a harmonized

(HAR) grounded 3-conductor cord, type H 0 5 V V - F , with conductors

listed below. A suitable cord end is required for connecting to the

equipment (see unit socket) and must terminate with an IEC approved

plug for proper connection to power supply.

RTE-111 and RTE-211

Nominal 1.5 mm

2

 cross section rated 16 Amps

Unit Socket: IEC - 320  C19

RTE-221

Nominal 1.0 mm

2

 cross section rated 10 Amps

Unit Socket: IEC - 320  C13

Summary of Contents for RTE-111

Page 1: ...nce or to any unit that has been operated or maintained in any way contrary to the operating or maintenance instructions specified in NESLAB s Instruction and Operation Manual This warranty does not c...

Page 2: ...ns 9 SECTION IV Temperature Controller Start Up 10 Controller Keypad Display 10 Changing a Value 11 Controller Displays 11 Operator s Loop 12 Setup Loop 13 Error Messages 15 Autorefill Optional 16 Hig...

Page 3: ...ted and found to be in good condition If the unit shows external or internal damage or does not operate properly contact the transportation company and file a damage claim Under ICC regulations this i...

Page 4: ...sible for the fluid used For 220 240 volt units supplied without a line cord use a harmonized HAR grounded 3 conductor cord type H 0 5 V V F with conductors listed below A suitable cord end is require...

Page 5: ...1 x 20 3 x 15 3 9 1 4 x 10 x 6 23 5 x 25 4 x 15 2 9 1 4 x 10 x 9 23 5 x 25 4 x 22 9 1 9 7 0 3 2 12 25 5 4 20 5 25 x 10 5 16 x 15 7 8 63 5 x 26 2 x 40 3 25 x 12 3 8 x 18 3 8 63 5 x 31 4 x 46 7 27 7 8 x...

Page 6: ...m ambient temperature of 95 F In terms of Celsius derate the cooling capacity 1 for every 0 5 C above 24 C to a maximum ambient temperature of 35 C Electrical Requirements Line voltage may be easily a...

Page 7: ...unit and the external system as short as possible and to use the largest diameter tubing practical Tubing should be straight and without bends If diameter reductions must be made make them at the inl...

Page 8: ...usted the pump inlet will draw an occasional air bubble to prevent over flow and the pump outlet will force fluid through the submerged tube to prevent aeration of the vessel To avoid siphoning the ba...

Page 9: ...page For operation from 30 C to 8 C a 50 50 mixture by volume of tap water and laboratory grade ethylene glycol is suggested Above 80 C and below 30 C the user is responsible for fluids used Never use...

Page 10: ...ystem Although the initial fill may be as high as 10 megohm cm compensated at 25 C the desired level for long time usage is 1 to 3 megohm cm compensated at 25 C The above two recommendations will redu...

Page 11: ...on The HEAT indicator flashes when the heater is pulsating A balance between COOL and HEAT controls the temperature NOTE Below 50 C the refrigeration system is on unless the setpoint is more than 2 C...

Page 12: ...plays An alphanumeric display presents numeric readings of various operating conditions within the bath Display function is selected by pressing the appro priate keys to move through a menu of availab...

Page 13: ...id temperature Press the NEXT ENTER key to view the setpoint SP displays the controller setpoint The display will flash between SP and the actual setpoint number Use the YES NO keys to change the setp...

Page 14: ...etup Loop if any key is not pressed during a one minute time span the controller will automatically return to the Operator s Loop tempera ture display NOTE If the unit exceeds either temperature limit...

Page 15: ...oop 2 of 2 Hit High Temperature Limit Lot Low Temperature Limit r232 RS232 Protocol bAUd BAUD rate factory value 9600 dAtA Data Bits factory value 8 StoP Stop Bit factory value 1 PAr Parity factory va...

Page 16: ...04 13 Interrupt Error Er14 Synchronous Error Er15 Asychronous Error Er16 Bad Calibration Er19 Low Temp Limit Er21 High Temp Limit Er23 RTD2 Shorted Er24 RTD2 Open Not Installed Er25 RTD1 Shorted Er26...

Page 17: ...e plumbing connection for the autorefill device labeled WATER INLET is located on the rear of the autorefill assembly The connection is 3 8 inch OD stainless steel Remove the nut and install the tubin...

Page 18: ...L SAFETY adjustment dial on the right side of the pump box Turn the dial fully clockwise and press the red RESET switch located next to the adjustment dial NOTE On units without a reset switch turn th...

Page 19: ...nsor Connections Pin Function 1 3 wire RTD connection A 2 No connection 3 No connection 4 3 wire RTD connection B 5 No connection 6 No connection 7 No connection 8 No connection 9 3 wire RTD connectio...

Page 20: ...denser will lead to a loss of cooling capacity Periodic vacuuming of the condenser is necessary To access the condenser the front grille must be removed The unit must be turned off before the front pa...

Page 21: ...screws two on each side securing the reservoir s cover To get slack on the refrigeration cable remove the cable strap The cable itself does not need to be disconnected Turn the cover assembly over an...

Page 22: ...or s loop Calibration loop Setup loop tunE C A L Chip Number Software Number Software Version Checksum Code N O N O HOLD N O HOLD 10 SECS N E X T E N T E R N E X T E N T E R N E X T E N T E R N E X T...

Page 23: ...or s Setup and Calibration Loops Go to the Setup Loop and place the unit in the internal or remote RTD mode of operation RTD1 Internal Probe RTD2 Remote Probe Return to the Operator s Loop adjust the...

Page 24: ...23 Figure 4 Calibration Loop rtd1 Internal sensor rtd2 remote sensor r1H High temperature r1L Low temperature Ain NA for this unit Aout NA for this unit Stor Store...

Page 25: ...or will short cycle clicking sound and no cooling will occur Proper ventilation is required for heat removal Make sure ventilation through the front and rear panels is not impeded and the panels are f...

Page 26: ...r based temperature control apparatus Choose upper or lower temperature limits and monitor system status with an alarm NEScom can also record your results on a user selectable graph NesCom must be use...

Page 27: ...cambiar el fluido refrigerante suba la temperatura de operaci n de la unidad para descongelar los serpentines de refrigeraci n Es necesario un vaciado peri dico de las aletas del condensador La frecue...

Reviews: