background image

Activation methods

11

Installation and Programming manual

START INPUT

The START ancillary input is completely programmable, therefore, it
can activate the sounder/flasher by means of either positive signals
(Applied/Removed) or negative signals (Applied/Removed).

STOP INPUT

The  STOP  signal  allows  you  to force  the  Ivy  unit to  standby  status
thus blocking all signalling. Once this signal is removed, the device
will  restart  the  evaluation  process  and  if  the  alarm  conditions  are
still active, it will trigger the respective signals.

Note

Although  the  STOP  input  is  fully  programmable,  the  manufacturer
strongly  recommends  an  “applied”  signal  configuration  rather  than  a
“removed” signal configuration, in order to avoid the risk of disablement
in the event of wire cutting.

LED INPUT

This  input  (activates  when  connected  to  negative)  operates  as  an
ancillary  channel  which  the  panel  can  use  to  activate  any  type  of
signal, in accordance with the configuration of the Ivy unit.

I-BUS

All I-BUS related activations must  be programmed via the intrusion
-control  panel.  Panel  events  are  capable  of  generating  signalling
directly  on  the  sounder/flasher,  without  activating  terminals  or
outputs.

Each event is capable of sending 8 programmable patterns to one or
more  Ivy-B  sounderflashers  configured  in  the  control  panel
“Outputs” or “Other outputs”.

Ivy-B  sounderflashers  can  be  deactivated  from  the  control  panel
using the previously mentioned conditions and also by means of the
“Stop  alarms”  shortcut,  when  the  control  panel  is  in  maintenance
status  with  the  appropriate  disarm  scenarios,  or  with  the  events
associated  with  the  5  possible  “Causes  of  cut  off”  (refer  to
paragraph

 5-3 Programming from a PC

).

3-2

Managing multi-alarm

conditions

There  is  no  priority  amongst  the  various  signals.  If  the  Ivy  unit
detects signals, it will activate the programmed signalling cycle and,
in the event of concurrent activations, add on the respective signals.

Restoral  of  a  detected  signal  annuls  the  respective  alarm  cycle
automatically,  but  it  does  not  annul  alarm  cycles  relating  to  other
signals.  The  Ivy  unit  will  restore  to  standby  status  when  all  alarm
conditions cease.

Summary of Contents for IVY series

Page 1: ...Innovative Electronic Solutions Ness IVY Self Powered Siren for Outdoor Use Installation Programming Manual ...

Page 2: ...uidelines 7 2 2 Wiring the device 7 2 3 Battery connections 9 Chapter 3 Activation methods 10 3 1 Types of signal 10 3 2 Managing multi alarm conditions 11 Chapter 4 Signalling 12 4 1 Types of signalling 12 4 2 Tamper memory and fault signalling 13 Chapter 5 Programming 14 5 1 The Programming steps 14 5 2 Programming Menu 15 5 3 Programming from a PC 17 Appendix A Order codes 20 Notes 21 Warranty ...

Page 3: ...tten permission of Ness Ness reserves the right to make changes to features and specifications at any time without prior notification in the interest of ongoing product development and improvement 2014 Ness Corporation Pty Ltd ABN 28 069 984 372 3 IVY SIREN Installation Programming Manual Document Part Number 890 450 www nesscorporation com National Customer Service Centre Ph 1300 551 991 customer...

Page 4: ... etc and ready to go factory settings refer to Table 7 Programming Menu ensure fast and easy installation with few or even no setting adjustments Ness Corporation also offers Ivy unit units which can be connected to SmartLiving intrusion control panels via I BUS for remote programming and management purposes thus providing first rate security system customization capabilities 1 1 Suppliers Details...

Page 5: ...rity FAULT Tamper signal relay with programmable polarity Super bright LED technology flasher with high power driver circuit Blow torch protection Magneto dynamic horn with automatic function control Dislodgement and Open casing protection Metal guard inside 4 tone sounder Squawk tone Programmable sound output time Programmable volume Programmable flasher sequence Programmable flasher time Backup ...

Page 6: ... M Wall plug locations N Tamper screw location O Metal guard screw locations P External casing screw locations Q STATUS LED Red LED R PRG LED Green LED S Magneto dynamic horn connector T External casing in plastic U Casing hinges V Metal guard Table 4 Terminal board no icon name Description 1 Positive power terminal supports 13 8V 2 Negative power terminal 3 START D Ancillary terminal with program...

Page 7: ...n is possible only for bus versions C D G H I K L M M M M N O O P P U U Table 5 Technical specifications Operating voltage nominal 13 8 V maximum 14 0 V minim 13 2 V Minimum current draw 15 mA Maximum current draw from panel 150 mA Maximum current draw from battery 900 mA Sounder output l 3m 104 dB A Carrier frequency 1148 Hz Flash rate per minute programmable 36 46 56 Maximum alarm time programma...

Page 8: ...e the device Note If the factory default settings suit the installation requirements device configuration will be unnecessary 10 Replace the metal guard and the plastic casing The STATUS LED will blink at 0 5 second intervals 11 Powerup the device The STATUS LED will go On solid for 10 seconds The LED will go Off when the Ivy unit enters the ope rating phase standby If the Ivy unit is connected vi...

Page 9: ... the sounder flasher from the intrusion control panel for example during maintenance sessions I BUS CONNECTION Only the Ivy BF can be connected to the I BUS connections on the Ness SmartLiving Series panels This connection allows you to program the device and activate alarm signalling directly from the panel In addition connection of the I BUS wire to terminal provides a power source which enables...

Page 10: ...equires a 12V 2 1Ah battery not included which must be connected by means of the respective wires Table 3 E Take care to respect the battery polarity during the installation phase red positive black negative The battery efficiency test will run 60 minutes after installation and every 10 minutes thereafter In the event of an alarm the battery test will be delayed by 60 minutes Failure of the batter...

Page 11: ...vy unit processes the signals it picks up and then generates the respective events which can be associated with one or more signals The Ivy unit can generate the following events Power failure Low battery Battery inefficient Open casing Device dislodgement Foam tamper or similar in the horn Blow torch tamper Horn damage I BUS loss Note The audible and visual signalling triggered by open casing foa...

Page 12: ...US All I BUS related activations must be programmed via the intrusion control panel Panel events are capable of generating signalling directly on the sounder flasher without activating terminals or outputs Each event is capable of sending 8 programmable patterns to one or more Ivy B sounderflashers configured in the control panel Outputs or Other outputs Ivy B sounderflashers can be deactivated fr...

Page 13: ...able 3 R These can be activated by the control panel events using SmartLeague software programme refer to paragraph 5 3 Programming from a PC These two LEDs if suitably programmed will signal device faults and tamper events for details refer to paragraph 4 2 Tamper memory and fault signalling AUDIBLE SIGNALLING The magneto dynamic horn provides a choice of 4 tones which can be programmed with a ma...

Page 14: ...table shows the various event types and how they are signalled on the LEDs the number of slow blinks which signal the type of event concerned and the related Programming menu option which will allow you to enable disable the respective signalling capacities Fault signalling will stop automatically when the cause of the fault clears Tamper memory signalling will clear only after two consecutive ala...

Page 15: ... exit the programming phase and step back to this point if no command is received within the allowed time 3 Press and hold the PAGE button until the STATUS LED goes Off 4 Use the PAGE button to move to the different options on the menu The LED combination the LEDs which blink identifies the option concerned 5 Press the SEL button Table 3 B to select the required option The LED combination the LEDs...

Page 16: ...utes 6 minutes 3 minutes 5 Flashes Blinking on the LEDs of the LED Input 50 flashes minute 42 flashes minute 33 flashes minute 6 Outputs TAMPER and FAULT TAMPER normally closed TAMPER normally open FAULT normally closed FAULT normally open 7 Activation of the START input LED STATUS LED PRG Visual signalling Sounder Deactivated empty 8 Activation of the LED input LED STATUS LED PRG Visual signallin...

Page 17: ...lect the type of sound emitted by the horn 4 Maximum audible signal time allows you to select the maximum time the horn will sound for after which only other types of signalling will continue until the Ivy unit restores to standby 5 Visual signals the first option allows blinking on the STATUS and PRG LEDs activated by the LED input the other options allow you to select the visual signal on the fl...

Page 18: ...asher activation Duration sounder sounder activation time expressed in seconds from 1 to 125 or in minutes from 1 to 125 Sound type the sound of the audible signal 5 tones available Volume 17 volume levels available Activate flasher enable disable flasher activation Duration flasher flasher activation time expressed in seconds minutes or Endless If Endless is selected the flasher will signal conti...

Page 19: ...d set the device parameters listed in this section which coincide with those describe in paragraph 5 2 Programming Menu Additionally the device provides the IBUS monitor parameter which when activated after control panel reset monitors the BUS for one minute The BUS status is indicated on the PRG LED On solid BUS disconnected 1 blink per second BUS connected and sounderflasher not enrolled 2 blink...

Page 20: ...s when the respective event is active If the Invert option is enabled LED activation occurs when the respective event is not active Note If the assigned event is a pulse event the Off status of the LED will occur only when you exit the control panel programming session SOUNDER FLASHER CUT OFF EVENTS In this final section you can select up to 5 control panel events which cut off the sounder and fla...

Page 21: ...20 Programming Installation and Programming manual ...

Reviews: